Siemens Simovert Masterdrives Compendium page 517

Motion control
Hide thumbs Also See for Simovert Masterdrives:
Table of Contents

Advertisement

03.2010
Example of
parameter identifier
Siemens AG
6SE7087-6QX70 (Version AL)
SIMOVERT MASTERDRIVES
Reply ID
0
No reply
1
Transfer parameter value in the case of non-indexed
parameters (word)
2
Transfer parameter value in the case of non-indexed
parameters (double word)
Transfer descriptive element 1
3
4
Transfer parameter value (array, word) in the case of indexed
parameters 2
5
Transfer parameter value (array, double word) in the case of
indexed parameters 2
6
Transfer number of array elements
7
Task cannot be executed (with error number)
8
No operator change rights for the PKW interface
9
Parameter change report (word) (not with the CBC)
10
Parameter change report (double word) (not with the CBC)
Parameter change report (array, word) 2 (not with the CBC)
11
Parameter change report (array, double word) 2 (not with the
12
CBC)
13
Reserved
14
Reserved
15
Transfer text (not with the CBC)
1
The required element of the parameter description is specified in IND (2nd word)
2
The required element of the indexed parameter is specified in IND (2nd word)
Table 8.4-6
Reply ID (converter -> master)
Source for the ON/OFF command (control word 1, bit 0): P554 (=22A
Hex)
Change parameter value (array, word) and store in the EEPROM.
1st word
Bit No.:
15
AK
Binary value
1
1
HEX value
C
Bits 12 to 15:
Value = 12 (= "C" Hex); change parameter value (array, word)
and store in the EEPROM
Bits 0 to 11:
Value = 554 (= "22A" Hex); parameter number without a set
parameter change report bit
Compendium Motion Control
Meaning
Parameter ID (PKE)
12 11
10
SPM
Byte 1
0
0
0
0 1 0
2
Communication / CBC
PNU
Byte 0
0 0 1 0
1
0
1 0
2
A
8.4-19
0

Hide quick links: