Communication / CBC
Potential
equalization
Laying cables
8.4-12
The shield must not
be exposed here!
15 mm
Adapt length to match
type of construction!
Fig. 8.4-11
Removing insulation from the cable when shield clamps are used
♦ Please avoid differences in potential (e.g. as a result of different
power supply levels) between the converters and the PROFIBUS-
DP master.
♦ Use equipotential bonding cables:
2
• 16 mm
Cu equipotential bonding cables up to 200 m
2
• 25 mm
Cu equipotential bonding cables over 200 m
♦ Route the equipotential bonding cables so that there is the smallest
possible surface between the equipotential bonding cables and
signal cables.
♦ Connect equipotential bonding cables to the ground/protective
conductor through the largest possible surface area.
Please comply with the following instructions when laying cables:
♦ Do not lay bus cables (signal cables) directly parallel to power
cables.
♦ Lay signal cables and the associated equipotential bonding cables
with the lowest possible distance between them and on the shortest
routes.
♦ Lay power cables and signal cables in separate cable ducts.
♦ Attach shields through a large surface area.
6SE7087-6QX70 (Version AL)
Compendium Motion Control
03.2010
Do not excessively
bend springs!
35
Shield
Converter housing
Siemens AG
SIMOVERT MASTERDRIVES