05.2003
3.5.2
Examples
Compact PLUS
type drive
Line supply cable
(non-shielded)
Radio
Load
interf.-
suppr.
filter
Connecting
Line reactor
adapter
Siemens AG
6SE7087-6QX70 (Version AD)
SIMOVERT MASTERDRIVES
Instructions for Design of Drives in Conformance with EMC Regulations
Rect.unit
Inv.
Inv.
SIEMENS
SIEMENS
SIEMENS
Run
Failure
Chopper
active
P
P
A
A
S1
S1
X101
B
X101
B
X103
C
X103
C
Shielded motor cable
Fig. 3-14
Example of a Compact PLUS type unit with radio interference suppression
filter and line reactor
The cabling should be kept as short as possible. The line supply cable
to the radio interference suppression filter must be routed separately
away from other cables (zone concept!).
The motor must be connected using a shielded cable! The shield has to
be connected through the largest possible surface area at the motor
and the inverter.
Compendium Motion Control
Mounting plate
e.g. galvanized
steel plate
Line
supply
cable
Radio inter-
ference
suppression
filter
Fan
Line
reactor
Connecting
adapter
Shielded motor cable
3-19