02.2004
Basic unit with
CUMC/CUPM/
CUVC/CUVP
Board
CUPM in Compact and
chassis type unit
CUMP in
Compact PLUS unit
CUMC in
Compact PLUS unit
CUMC in Compact and
chassis type unit
CUVC in Compact and
chassis type unit
CUVP in
Compact PLUS unit
NOTICE
SCB 2
supplementary
board
NOTE
Siemens AG
6SE7087-6QX70 (Version AD)
SIMOVERT MASTERDRIVES
In the SIMOVERT MASTERDRIVES MC series, the control electronics
board, CUMC (Control Unit Motion Control), CUPM (Control Unit
Motion Control Performance 2), CUMP (Control Unit Motion Control
Compact PLUS Performance 2), CUVC (Control Unit Vector Control) or
CUVP (Control Unit Vector Control Compact PLUS) is used. Depending
on the type of basic unit, it has at least one serial interface with the
USS protocol. The following table shows the available interfaces:
Number of interfaces Physical interface
2 interfaces with USS
protocol
Designation: SCom1
and SCom2
1 interface with USS
protocol
Designation: SCom1
1 interface with USS
protocol
Designation: SCom1
2 interfaces with USS
protocol
Designation: SCom1
and SCom2
2 interfaces with USS
protocol
Designation: SCom1
and SCom2
2 interfaces with USS
protocol
Designation: SCom1
and SCom2
Table 8.1-9
Interfaces on the CU board
All the interfaces on the CU boards are non floating (not electrically
isolated).
The SCB2 (Serial Communications Board) is an expansion board of the
SIMOVERT MASTERDRIVES. The board has a floating RS485
interface. Either the peer-to-peer protocol or the USS protocol can be
used at this interface.
The supplementary SCB2 board cannot be built into the Compact
PLUS type of unit.
Compendium Motion Control
RS485 / 2-wire on terminal strip X103
(SCom1 and SCom2)
or
RS232 or RS485 / 2-wire at 9-pole SUB-D
socket X300 (SCom1)
RS485 / 2-wire at terminal strip X100
or
RS232 or RS485 / 2-wire at 9-pole SUB-D
socket X103
RS485 / 2-wire at terminal strip X100
or
RS232 or RS485 / 2-wire at 9-pole SUB-D
socket X103
RS485 / 2-wire on terminal strip X103
(SCom1 and SCom2)
or
RS232 or RS485 / 2-wire at 9-pole SUB-D
socket X300 (SCom1)
RS485 / 2-wire on terminal strip X101
(SCom2)
and
RS232 or RS485 / 2-wire at 9-pole SUB-D
socket X300 (SCom1)
RS485 / 2-wire on terminal strip X100
(SCom2)
and
RS232 (SCom1) or RS485 / 2-wire
(SCom2) at 9-pole SUB-D socket X103
Communication / USS
Baud rate
[kBit/s]
max. 38.4
max. 38.4
max. 38.4
max. 38.4
max. 38.4
max. 38.4
8.1-21