05.2006
Bit 10: Control from the PLC command (H "control from the PLC")
Condition
Result
NOTE
Bit 11: Clockwise rotating field command (H "clockwise rotating field")
Condition
Result
Bit 12: Counter-clockwise rotating field command (H "counter-clockwise rotating field")
Condition
Result
NOTE
Bit 13: Command to raise the motorized potentiometer (H "raise motorized
potentiometer")
Condition
Result
Bit 14: Command to lower the motorized potentiometer (H "lower motorized
potentiometer")
Condition
Result
Siemens AG
6SE7087-6QX70 (Version AG)
SIMOVERT MASTERDRIVES
HIGH signal; the process data PZD (control word, setpoints) are only
evaluated if the command has been accepted; this data is sent via the
SST1/2 interface of the CUPM, the CB/TB interface (option) and the
SCB2 interface (option). In the case of Compact Plus, the SST1/2 inter-
face is on the basic board; the TB and SCB2 interfaces do not exist.
♦ If several interfaces are used, only the process data of the interfaces
are evaluated, which send an H signal.
♦ For an L signal, the last values are received in the appropriate dual
port RAM of the interface.
An H signal appears in the visualization parameter r550 "control word
1", if one of the interfaces sends an H signal!
HIGH signal
♦ The setpoint is influenced in conjunction with bit 12 "counter-
clockwise rotating field".
Refer to the function diagram "Setpoint processing (Part 1)" (310)
HIGH signal
♦ The setpoint is influenced in conjunction with bit 11 "clockwise-
rotating field".
Refer to the function diagram "Setpoint processing (Part 1)" (310)
The counter-clockwise rotating field and the clockwise rotating
field command have no influence on supplementary setpoint 2, which
is added after the ramp-function generator (RFG)!
HIGH signal
♦ The motorized potentiometer in the setpoint channel is driven in
conjunction with bit 14 "motorized potentiometer, lower".
Refer to the function diagram "Motorized potentiometer" (300)
HIGH signal
♦ The motorized potentiometer in the setpoint channel is driven in
conjunction with bit 13 "raisemotorized potentiometer".
Refer to the function diagram "Motorized potentiometer" (300)
Compendium Motion Control