02.2004
NOTE
Bus connection via
terminal strip
Higher-level
computer (master)
S1
with activated
bus termination
36 35 34 33
Connect
Shield
Siemens AG
6SE7087-6QX70 (Version AD)
SIMOVERT MASTERDRIVES
♦ When the unit is supplied, the terminating resistors are not switched
in!
♦ Please note that the bus termination is switched in only at the first
bus node (e.g. SIMATIC S 5/CP524) and last bus node (e.g.
CUPM)! When the matching resistors are being set, the electronics
box must be isolated from supply!
♦ Data transmission faults possible on the bus!
During active bus operation, the units with a switched-in
terminating resistor must not be disconnected from supply. The
matching resistor when disconnected from supply (off-load) is no
longer effective because the terminating resistor obtains its voltage
from the connected unit.
The following illustration shows an example of the bus connection at
terminal strip X100 (Compact PLUS). If the connector at terminal strip
X100 of one node is removed, data transfer via bus is not interrupted.
The other nodes on the bus continue to be supplied with data via the
bus.
S la v e 1
S la v e 2
S1
ON
OFF
ON
X 1 0 0
X 1 0 0
36 35 34 33
Connect shield to
converter housing
Fig. 8.1-14
Connection of the 2-wire bus cable at terminal strip X100
(Compact PLUS)
Compendium Motion Control
S la v e n
S1
OFF
ON
OFF
X 1 0 0
36 35 34 33
Communication / USS
Last slave,
bus termination
activated
8.1-29