09.2008
Siemens AG
6SE7087-6QX70 (Version AK)
SIMOVERT MASTERDRIVES
3. Set the characteristic to meet requirement "Maximum torque in field
weakening range remains constant":
The output voltage (r003) at the field weakening activation speed
under no load conditions must be measured. The output voltage at
the end point of the desired field weakening range must then be
calculated according to the following formula from the maximum
converter output voltage (depends on converter supply voltage) and
the calculated output voltage at the field weakening activation
speed:
=
U
U
Conv
Out
nEnd
Conv
where
=
U
350
V
(
Conv
max
=
U
Output
Conv
Out
nEnd
=
U
Output
Conv
Out
nAct
n
=
End
k
Field
weakening
f
n
Act
w
eakening
The formula is based on the simplified principle that the voltage drop
across the winding resistance of the motor is negligible in the field
weakening range. This applies to series 1FT6 and 1FK7 servo
motors.
The output voltage calculated by this formula must then be set at the
end speed of the field weakening range at no load via the short-
circuit current. The current setting must be increased in relation to
the automatically calculated value, as the automatic arameterization
run defines the short-circuit current for operation at constant
maximum output.
100
90
80
70
60
50
40
30
20
10
0
0
500
1000
e.g. 1FT6086-8AF71, 27.5 Nm at 2900 rev/min to 4500 rev/min,
U
= 296 V, U
(no load 2900)
Compendium Motion Control
(
)
2
2
+
1
k
U
max
f
Conv
=
when
UDCL
540
V
)
v
oltage
at
end
of
field
voltage
at
field
weakening
range
:
Ratio
speed
a
nd
field
weakening
1FT6086 - 8AF71
1500
2000
2500
Speed [min-1]
= 174 V I
(no load 4500)
Functions
2
2
k
Out
nAct
f
weakening
range
activation
speed
between
final
field
activation
speed
Field
weakening
activation point
3000
3500
4000
(P105) = 60 A
k
4500
7-69