Parameter
Display parameters
r007
n124
P123
U123
Setting parameters
0 ...120 %
Setting parameter, not indexed
U345 (50.00)
(factory setting 50.00 %)
Range: 0 ... 120 %
Setting parameter, indexed, index 3
U345.3
Setting parameter, belongs to BICO
U345.B
data set (2 indices)
Setting parameter, belongs to the
U355.F
function data set (4 indices)
Connectors/binectors
Connector (freely interconnectable 16-bit
K0001
signal; number representation:
100% corresponds to 4000 hex which
corresponds to 16384dec)
Double connector (freely interconnectable
KK0002
32-bit signal; number representation:
200% corresponds to 4000 0000hex which
corresponds to 2 147 483 647dec)
Binector (freely interconnectable digital
B0000
signal)
Output via dig. output [90], [91], [92]
P531 (326)
Selection of any connector (factory setting:
K
P531=326, i.e. connector K326 selected)
Place for entering the selected connector
Selection of any double connector
P432 (546)
(factory setting: P432=546, i.e. connector
KK
KK546 selected)
1
2
Explanation
Symbols of the function diagram
Explanation of the symbols used in the function diagram
P597 (1)
.01
Selection of three binectors via indexed
B
.02
parameters (binector B0001 is the selected
B
.03
factory setting for all three outputs, i.e. fixed value
B
"1", see below)
0
B0000
B0001
1
0%
K0000
100%
K0001
(=16384)
200%
K0002
(=32767)
-100%
K0003
(=-16384)
-200%
K0004
(=-32767)
0
KK0000
100%
KK0001
(=1 073 741 824)
200%
KK0002
(=2 147 483 647)
-100%
KK0003
(=-1 073 741 824)
-200%
KK0004
(=-2 147 483 647)
3
4
Automatic conversion between connectors and
double connectors
Converting a connector to a double connector
K0139
K0139 is converted to a double connector by entering it in
the high word of the double connector and by setting its
LOW word to zero.
Converting a double connector to a connector
KK0149
KK0149 is converted into a connector by entering its high
word in the connector.
Cross references
[702.5]
Indication of the block number and the
sampling time for the free blocks
U953.14 = ___(xx)
n959.14 = 7
Calculating time of the free blocks
{8 s}
5
6
V2.5
Function diagram
fp_mc_015_e.vsd
MASTERDRIVES MC
17.12.03
U531
KK
U584
K
The signal comes from / goes to page 702,
signal path 5 of the function diagram.
The block has the number 314. The block
can be activated via U953.14 and its
sampling time selected (see sheet 702).
The block is permanently assigned to a sampling
time.
Blocks of the indicated type require a typical
sampling time of approximately 8 ms (rough
guide value).
If the total available calculating time is
exceeded, the monitoring system shown on
sheet 702 will respond.
7
8
- 15 -