Siemens Simovert Masterdrives Compendium page 102

Motion control
Hide thumbs Also See for Simovert Masterdrives:
Table of Contents

Advertisement

05.2003
Rule 15
Rule 16
Rule 17
Rule 18
Rule 19
Rule 20
Siemens AG
6SE7087-6QX70 (Version AD)
SIMOVERT MASTERDRIVES
Instructions for Design of Drives in Conformance with EMC Regulations
A noise suppression filter should always be placed close to the fault
source. The filter must be connected to the cabinet housing, mounting
panel, etc. through a large surface area. A bare metal mounting panel
(e.g. manufactured from stainless steel, galvanized steel) is best, as
electrical contact is established through the entire mounting surface. If
the mounting panel is painted, the paint has to be removed at the screw
mounting points for the frequency converter and the noise suppression
filter to ensure good electrical contact.
The incoming and outgoing cables of the radio interference suppression
filter have to be spatially separated/isolated.
In order to limit the noise emitted, all variable-speed motors have to be
connected-up using shielded cables, with the shields being connected
to the respective housings at both ends in a low-inductive manner
(through the largest possible surface area). The motor feeder cables
also have to be shielded inside the cabinet or at least shielded using
grounded partitions. Suitable motor feeder cable e.g. Siemens
PROTOFLEX-EMV-CY (4 x 1.5 mm
Cables with steel shields are unsuitable.
A suitable PG gland with shield connection can be used at the motor to
connect the shield. It should also be ensured that there is a low-
impedance connection between the motor terminal box and the motor
housing. If required, connect-up using an additional grounding
conductor. Do not use plastic motor terminal boxes!
A line reactor has to be installed between the radio interference
suppression filter and the SIMOVERT MASTERDRIVES.
The line supply cable has to be spatially separated from the motor
feeder cables, e.g. by grounded partitions.
The shield between the motor and SIMOVERT MASTERDRIVES must
not be interrupted by the installation of components such as output
reactors, sinusoidal filters, dv/dt filters, fuses, contactors. The
components must be mounted on a mounting panel which
simultaneously serves as the shield connection for the incoming and
outgoing motor cables. Grounded partitions may be necessary to shield
the components.
In order to limit the radio interference (especially for limit value class
"First environment "), in addition to the line supply cable, all cables
externally connected to the cabinet must be shielded.
Examples of these basic rules:
Compendium Motion Control
2
2
... 4 x 120 mm
) with Cu shield.
3-15

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents