Siemens Simovert Masterdrives Compendium page 108

Motion control
Hide thumbs Also See for Simovert Masterdrives:
Table of Contents

Advertisement

05.2003
Drive unit of
Compact type
Line reactor
Load
Radio in-
terference
suppression
filter
Mains
Line
supply
cable
(non-
shielded)
Siemens AG
6SE7087-6QX70 (Version AD)
SIMOVERT MASTERDRIVES
Instructions for Design of Drives in Conformance with EMC Regulations
Options
e.g. braking
unit
Mounting panel
e.g. galvanized
steel plate
Connecting
adapter
Shielded motor cable
Fig. 3-16
Example of a Compact type unit with radio interference suppression filter
and line reactor
The cabling should be kept as short as possible. The line supply cable
to the radio interference suppression filter must be routed separately
away from other cables (zone concept!).
The motor must be connected using a shielded cable! The shield must
be connected through the largest possible surface area at the motor
and drive converter. The optional connecting adapter can be used to
connect the shield to SIMOVERT MASTERDRIVES.
Compendium Motion Control
Line
reactor
Radio interference
suppression filter
Connecting
adapter
Shielded
motor cable
Line supply
cable
3-21

Hide quick links:

Advertisement

Table of Contents
loading