Configuration in the RE
1. Open the released master recipe in the RE for editing.
2. Open an ROP, "Exception Test" in this case.
3. Insert the "Monitoring" recipe object into your recipe. Use the Insert > Monitoring menu
command or the corresponding icon of the "Insert" toolbar. Then click on the connecting
line between the start and end steps.
4. Double-click on the "Monitoring" title in the monitoring with the "Selection" setting. The
default structure of the monitoring opens. The default structure contains a loop. The left
transition is the monitoring condition and the right one is the repeat condition. All
subsequent recipe objects are inserted on the left connecting line after the monitoring
condition.
5. Insert a recipe phase in the monitored area (light red frame) and select the "filling (EPH)"
function in the properties dialog of the recipe phase.
6. Insert a command step in your monitoring (red frame).
7. Insert an operator instruction into your monitoring.
8. Insert a jump into your monitoring.
9. Insert a recipe phase into your monitoring.
Interim result
You have now inserted all the required recipe elements into your example recipe. Now
configure the inserted recipe objects.
Configuration of the recipe objects
1. Configure the start condition T 2 for the monitoring, Transition 2. Operand 1 is the RPE
status and Operand 2 is a constant. Select the recipe element "filling_1" and leave the
"Status" attribute as is. Select the "running" value for Operand 2 and close all dialogs.
2. Configure command step 3 in the monitoring. The command step should be used to abort
the "filling" recipe phase. Select the "filling_1" recipe phase and move it to the right window.
Select "Cancel" under the commands. Close the dialog.
3. Configure Transition 4. The transition should include a prompt asking if the "filling_1" recipe
phase is to be aborted. Operand 1 is the RPE status and Operand 2 is a constant. Select
the recipe element "filling_1" in the monitoring and leave the "Status" attribute as is. Select
the "aborted" value for Operand 2 and close all dialogs.
4. Configure the operator instruction in the "Instruction" tab of the properties dialog. The entry
in the "Order" box may read as follows. "Check recipe element "filling_1". Close the dialog.
5. Configure Transition 9. The monitoring should now be completed. For this to happen,
Transition 9 can never be fulfilled. Operand 1 is the RPE status and Operand 2 is a constant.
Select the recipe element "filling_1" and leave the "Status" attribute as is. Select the
"running" value for Operand 2 and close all dialogs.