3.10 Plant update
● As of SIMATIC BATCH V7.0, enumerations are supported for the BOOL data type. If you
use this type, now it will be interpreted as ENUM and no longer as BOOL. This results in a
type change during generation, which means that the plausibility check will mark the release
of such recipe objects as invalid when you update the plant in BatchCC. If you want to use
recipe parameters of the Enumeration data type in master recipes, configure the ENUM
data type instead of BOOL in the PCS 7 engineering.
● If you have configured a redundancy status display of the SIMATIC BATCH server in a
process picture on a WinCC client in a previous version of SIMATIC BATCH, it must be
removed in order to update the system to SIMATIC BATCH V8.2. Instead, use the icons in
the status bar of BatchCC to display and check the status of the BATCH server.
Software update
You can update PCS 7 projects of the following SIMATIC BATCH versions SIMATIC BATCH
V8.2:
● SB AS based
– SB AS based V6.1 (incl. SPs and HFs) (only with Siemens Support)
– SB AS based V7.0 (incl. SPs and HFs)
● SB
– SB V6.0 (up to SP3 and HFs) via SB V6.0 via SB V6.1 SP3
– SB 7.0 (incl. SPs and HFs)
– SB 7.1 (incl. SPs and HFs)
– SB V8.0 (incl. SPs and UPDs)
– SB V8.1 (incl. SPs and UPDs)
Special notes
If the software was updated from one of the following versions to SB V8.0, SB V8.1 or SB V8.2,
the SB data can only be updated using Restore (in the BCC).
● SB V6.0 (up to SP4 including HFs)
● SB V6.1 (incl. SP3 and HFs)
● SB V7.0 (incl. SP1 and HFs)
● SB V7.1 (incl. SP1 and HFs)
● SB V7.1 (incl. SP2 and HFs)
Preparations for a software update
1. Archive closed batches in the BATCH Control Center.
2. Create a backup of your BATCH process cell in the BATCH Control Center.
3. Archive your PCS 7 project in the SIMATIC Manager.
4. If necessary, replace existing hardware, such as PC, AS memory, network adapters.