14.1 Dialogs
Image 14-5
Procedure
1. Click "New" to insert a new condition and configure it by pressing "Change". The new
condition is linked by default with "AND".
2. Click the first "AND" operator button and then "New" to insert a new condition line with an
AND operation. Then click "Change" to configure the condition.
3. Click the second "AND" operator button, insert a new condition, and configure it.
4. Click the first lower "AND" operator button and insert an empty condition. Click "Change"
to configure the condition.
5. Right-click the second operator button and change the operator to "OR" in the shortcut
menu.
Result:
You have created a two-level combination logic for your conditions.
Image 14-6
The first partial result is fulfilled, when the first two conditions are fulfilled. The second partial
result is fulfilled, when conditions 3 and 4 are fulfilled. The total result for the transition is fulfilled,
when either the first or the second partial result is fulfilled.
Dialog buttons
● OK: Saves your entries and closes the dialog.
● Print: Prints the conditions listed on the screen in tabular form immediately to the configured
printer.
● Change: The button has a variety of meanings depending on context. For recipe
engineering in the Recipe Editor, click the "Change" button to open the interactive dialog
for entering a condition previously created with the "New" button. In batch mode, you can
use this button to change the value of a constant in the control recipe.
● New: Click the "New" button to insert new rows for additional transitions. The button is only
available in the Recipe Editor.
832
Two-level combination logic for transition conditions
Result of interconnected conditions