Siemens SIMATIC BATCH Operating Manual page 128

Process control system pcs 7
Table of Contents

Advertisement

Engineering
7.1 Basic engineering for PCS 7
Procedure in the SIMATIC Manager
1. Select the project in the component view.
2. Select the menu item Insert > Station > SIMATIC PC Station.
Result: A new SIMATIC PC station is inserted in the current project.
3. Set the computer name of the PC station.
– To do this, select the SIMATIC PC station.
– Select the menu item Edit > Object Properties.
– Enter the computer name in the last field.
4. Follow the same procedure and install a SIMATIC PC station for each additional BATCH
client in the project.
5. Configure these SIMATIC PC stations in HW Config.
– To do this, select the SIMATIC PC station.
– Select the menu item Edit > Open Object.
– Insert a batch client application from the hardware catalog: On a BATCH client, you
6. Select the menu item Station > Save and Compile.
128
Result: HW config opens.
insert an additional WinCC application if the BATCH client is operated along with an OS
client on one PC.
Path in the hardware catalog: Standard > SIMATIC PC Station > HMI > BATCH
application client.
SIMATIC BATCH V8.2
Operating Manual, 02/2016, A5E35958174-AA