Requirements
1. Make sure that a dedicated SQL server instance is available for archiving.
Obtain support from your system database administrator.
2. The SQL server instance must have read and write rights for the "SIMATIC BATCH" user
group.
Obtain support from your system database administrator.
3. The user currently logged into the operating system must have administrator rights for the
SQL server instance.
Note
The use of already existing SQL server instances (e.g. from WinCC or PH) is not permitted.
Procedure
1. Start the local SQL server.
2. In BCC, select the menu command [Options] > [Settings] > [Project settings]
3. Select the "Archive" tab
4. Activate the "SQL Server:" check box.
5. Click on the "Create..." button.
6. The "Create SQL Server Database" dialog box opens.
7. Click on the "Create database" button.
8. The "Select directory" dialog box opens.
9. Select a directory for the database.
10.Click on the "OK" button.
11.The "SQL Server Login" dialog box opens.
– Select the SQL server from the drop-down list.
– Enable the "Use trusted connection" check box.
12.Click on the "OK" button.
Result
The local database of the SQL server is set up.
With the steps described above obtain support from your system database administrator.
SIMATIC BATCH V8.2
Operating Manual, 02/2016, A5E35958174-AA
9.9 Report creation and archiving of batch data
BATCH Control Center