Siemens SIMATIC BATCH Operating Manual page 703

Process control system pcs 7
Table of Contents

Advertisement

7. In the dialog that opens, specify the parameter groups to which you want to assign the
given parameters. You can find additional information in the online help. With recipe
engineering, only the parameters selected here are made available for a selected
parameter group.
Note
The selection made here always refers to the entire batch process cell.
Image 12-15 Parameter group assignment of the batch process cell
8. Download your process cell data to the BATCH server. To do so, select your process cell
and select "Download" in the shortcut menu.
Recipe engineering
1. Make sure that the project was activated on the PCS 7 OS and on the BATCH server and
then open BatchCC.
2. Update the process cell data in BatchCC.
3. Select an existing master recipe and cancel its release, if necessary. Then open it in the
Recipe Editor.
4. The existing master recipe is now extended by a parameter step and a parameter query in
the Recipe Editor (as an example). The means the unit procedure Reactor R501 is being
processed.
5. Insert a new recipe function. In the properties, select "Unit" under function and one of the
configured control strategies for control strategy.
SIMATIC BATCH V8.2
Operating Manual, 02/2016, A5E35958174-AA
12.8 How do I configure and use dynamic unit parameters?
Recommended procedure
703