Siemens SIMATIC BATCH Operating Manual page 1030

Process control system pcs 7
Table of Contents

Advertisement

Context help references
14.1 Dialogs
Runtime name
High limit
(not applicable for data types
Boolean, String, and user data
type)
Low limit (not applicable for
data types Boolean, String,
and user data type)
Setpoint
Created by
"Parameters" button
Block
Buttons
Check validity
Update
1030
This consists of a prefix (symbolic computer name of the OS station)
and the path to the WinCC tag, separated by ::.
Example: OS1_KH1D331::Process cell1/Unit1/CFC/EPH
ParameterName
The high limit of the setpoint is specified here.
The low limit of the setpoint is specified here.
The setpoint is specified here. In doing so, the following applies: Low
limit ≤ setpoint ≤ high limit. Only valid values are allowed.
Specification of the application that created the object, either SIMATIC
BATCH PCell Control Center or SIMATIC Manager.
● If a type object was created by SIMATIC Manager, additional
subobjects cannot be added, nor can the selected object be
deleted or changed, either via the PCC API or with the PCC
configuration dialog.
● If an instance object was created by SIMATIC Manager, additional
subobjects can be added via the PCC API or with the PCC
configuration dialog. However, it is still not possible to delete or
change the selected object here.
Activating this button takes you to the corresponding phase type pa‐
rameter. With the Back button of the phase type parameter, you return
to this location.
All batch instances, starting with the selected object (here, a parameter of
an equipment phase), are checked for consistency with the batch types and
for conformity to ISA-88. The validity errors and validity warnings are dis‐
played in the log field and can be visualized using the "Display" button.
All batch instances are adapted according to the batch types. This action
is always required if a change has been made to batch types of existing
batch instances (e.g., inserting a new parameter, changing the unit of
measure, etc.).
SIMATIC BATCH V8.2
Operating Manual, 02/2016, A5E35958174-AA