Siemens SIMATIC BATCH Operating Manual page 160

Process control system pcs 7
Table of Contents

Advertisement

Engineering
7.1 Basic engineering for PCS 7
● If you select an instance of this type, you can open and edit it within the CFC chart using
the "Open" shortcut menu command.
● The interconnection is possible with the control module level (CMs), the interlock logic and
batch control.
● In the SFC, in addition to the name of the operation/phase type parameter, an I/O name
must be specified for the SFC type in the characteristics view for setpoints. One setpoint
results in several block I/Os:
I/O name
<name>
<name>_Q
<name>_AI
<name>_ AO
<name>_M
<name>_MQ
<name>_MAI
<name>_MAO
<name>_B
<name>_BQ
<name>_BAI
<name>_BAO
* Only for PI or PO data types
● The following block I/Os exist for the control strategy:
I/O name
CS
QCS
● Set Enable bits in SFCs
Rules for supplying the equipment procedural elements with Batch data
Equipment procedural elements controlled by SIMATIC BATCH must be supplied with the
Batch data. The faceplates on the PCS 7 OS then indicate whether this equipment procedural
element is being used by SIMATIC BATCH and which batch is running. The batch name and
the batch ID are included in the messages to the PCS 7 OS.
To allow this, the five following interconnections must be configured:
SFC type
QBA_EN
QOCCUPIED
QBA_ID
QBA_NA
QSTEP_NO
160
Meaning
(IN)
Setpoint from SIMATIC BATCH or PCS 7 OS
(OUT)
Setpoint (valid value for SFC)
(IN)
Process value return input for process value
(OUT)
Process value for SIMATIC BATCH and PCS 7 OS
(IN)
Material code setpoint from SIMATIC BATCH*
(OUT)
Material code (valid MatCode for SFC)*
(IN)
Material code process value return input*
(OUT)
Material code process value for PCS 7 OS*
(IN)
Reserved for batch ID, currently not used*
(OUT)
Reserved for batch ID, currently not used*
(IN)
Reserved for batch ID, currently not used*
(OUT)
Reserved for batch ID, currently not used*
Meaning
(IN)
Control strategy setpoint from SIMATIC BATCH or PCS 7 OS
(OUT)
Control strategy (valid control strategy for SFC)
Automation function for example MEAS_MON, MO‐
TOR...
BA_EN
OCCUPIED
BA_ID
BA_NA
STEP_NO
Operating Manual, 02/2016, A5E35958174-AA