7.1.4.6

Setting up the equipment module with interface blocks IEPH and IEOP

SIMATIC BATCH block library
All the necessary BATCH blocks for the two modes are contained in the SIMATIC BATCH
block library. The documentation in the form of a PDF file is available under START > SIMATIC
> Documentation > English > SIMATIC BATCH. You can obtain direct help for each individual
block with the F1 key in the SIMATIC Manager in CFC when the BATCH block is selected in
the relevant library. The BATCH interface blocks are inserted in the CFC charts by dragging
them from the BATCH block library.
Overview of the BATCH interface blocks
Block
IEPH
IEOP
UNIT_PLC
TAG_COLL
IEPAR_DINT
IEPAR_BOOL
IEPAR_REAL
IEPAR_STR
IEPAR_PI
IEPAR_PO
IEPAR_ENUM
IEPAR_SOURCE
IEPAR_DEST
IEPAR_VIA
Equipment module
Using the BATCH interface blocks along with SIMATIC BATCH, makes the following functions
available:
● Controlling the running of the process:
The IEPH/IEOP blocks are used for this purpose. These provide the commands (for
example start or hold) of the recipe steps from the batch control to the processing blocks
(for example: SFC external view or user blocks). The processing blocks report their current
statuses back to the batch control.
● Transferring setpoints and process values:
The IEPAR blocks are used for this purpose. The batch control writes the recipe parameters
(setpoints) for the processing blocks into these blocks. The processing blocks write the
result data (process values) to the IEPAR blocks so that they can be stored as batch data
by the batch control. The IEPAR blocks linked to the IEPH/IEOP blocks are also used to
form transition conditions.
SIMATIC BATCH V8.2
Operating Manual, 02/2016, A5E35958174-AA
Application
Control of simple processes
Control of complex processes
Management of unit allocation
Collecting of process values for archiving, report creation and forming transi‐
tions
Parameter block for the data type double integer
Parameter block for the data type Boolean (binary)
Parameter block for the data type real (floating point)
Parameter block for the data type string (text)
Parameter block for the data type process input(input material)
Parameter block for the data type process output
Parameter block for the data type enumeration type (user-defined enumera‐
tion type)
Parameter block for the data type Source
Parameter block for the data type Dest
Parameter block for the data type Via
Engineering
7.1 Basic engineering for PCS 7