In the component view, below the configured SIMATIC PC station, you will see the following
object.
7.1.2.5

Adapting the CPU for AS-based mode

Adapt local data
The memory requirements of the local data of your CPU must be calculated for AS-based
mode and then possibly adapted. This is necessary for every CPU in your PCS 7 project.
Procedure
1. Open any CFC chart in the relevant S7 program.
2. Select the menu item Options > Chart Reference Data.
3. Select the menu item View > Local Data.
4. Use the local data table that is displayed in the steps described below.
5. Open your project with the component view in SIMATIC Manager.
6. In the SIMATIC manager, open the HWConfig. hardware configuration
7. Select the CPU in the rack.
8. Use the shortcut menu to select the object properties of the CPU.
9. Click on the "Memory" tab in the open dialog. You will see the local data arranged in priority
classes.
10.Adapt the amount of memory for the local data in accordance with the displayed local data
referred to in point 4.
Note
Optimization of local data
Use the procedure described above to optimize your local data within the priority classes
SIMATIC BATCH V8.2
Operating Manual, 02/2016, A5E35958174-AA
Engineering
7.1 Basic engineering for PCS 7
129