Siemens SIMATIC BATCH Operating Manual page 237

Process control system pcs 7
Table of Contents

Advertisement

6. Include the project in the CMP.
In the SIMATIC Manager > select the multiproject folder > In the shortcut menu >
Multiproject > Insert into Multiproject > User Objects tab > select project > OK. Optionally:
Browse and navigate to the corresponding path.
7. Merge the Ethernet subnets.
In the SIMATIC Manager > select the multiproject folder > In the shortcut menu, >
Multiproject > Adjust Projects > select Ethernet > Execute > select subnet in the multiproject
> Merge with right arrow > OK > Apply.
8. Check if the S7 connection between the AS and the OS, which was deleted in the DMP, is
now in the CMP. Save NetPro.
– Open NetPro, select the CPU in the AS and check the S7 connection in the connection
– Select the WinCC application on the OS and check the S7 connection in the connection
9. Add the batch process cell and the ISA-88 type definition.
– In the Plant view of the SIMATIC Manager > Select the project > In the shortcut menu
– Select the process cell folder in the Plant view > In the shortcut menu > Object properties
10.Check whether the name of the Batch process cell is identical to the name of the Batch
process cell at the MP level in all projects in the CMP.
In the plant view of the SIMATIC Manager, check the hierarchy names and the Batch
process cell names in the entire MP.
11.Compile and download the AS objects (CFC charts) and the OS objects of your multiproject.
12.Update the batch process cell, generate and propagate the batch types, merge the batch
instances, transfer the messages to the OS and load the batch data.
13.Update the batch data in the Batch Control Center (BCC).
Result
You have integrated the project back into the original CMP. You have made all the preparations
to start process mode in you project.
SIMATIC BATCH V8.2
Operating Manual, 02/2016, A5E35958174-AA
table.
table.
> Insert new object > Batch process cell.
> "S88 type definition" tab > select object type "Process cell" > OK. The folder of the
batch process cell is given a light green color.
Rational engineering
8.5 Distributed multiproject engineering
237