Before setting the communication specifications, set the "Serial (Ethernet)" communication module to "PLC link
(SYSMAC CS/CJ/CP/One)" (or to "PLC link (MELSEC Q series)" in the case of a PLC by Mitsubishi Electric
Corporation), save the setting, and then restart the system. When the system is restarted, the communication
settings are initialized.
Reference:
Use the same communication specification settings for the controller and the external device.
When making system settings/Ethernet settings, do not send external input into the Ethernet.
1.
On the Main screen, tap the [System] menu - [Communication] - [Ethernet(PLC Link)].
The Ethernet window is displayed.
2.
In the communication setting area, set the following items.
7
Setting item
Address setting
364
Communicating through Serial Communication (PLC Link)
Setting the Start-up Status [Startup Setting] (p.347)
Setting value
[Factory default]
Obtain an IP address
automatically
[Use the following IP address]
a.b.c.d
a: 1 to 223
b: 0 to 255
IP address
c: 0 to 255
d: 0 to 255
[10.5.5.100]
Description
Set the IP address of the controller.
When "Obtain an IP address automatically"
is selected, the IP address of the controller
will be automatically obtained.
When "Use the following IP address" is
selected, set the IP address, subnet mask,
and the default gateway address.
Input the controller IP address.