Appendix C — Specifications
Power Consumption and Cooling Requirements
The power and cooling requirements for the library depend on the number
and type of drives installed. The following table provides the maximum
power consumption and heat load for the base library and for each
additional component added to the base library. Use this information to
calculate the total maximum power consumption and heat load values,
which can be used to build a power budget for the library.
All values are measured at the AC input and include power supply
efficiency. The values are averages of observed hardware. In general, the
lighter the load on the power supplies, the less efficient they are. The
power supply efficiency in turn affects the power draw of all components.
November 2020
Component
Minimum Library (3-frame
a
with service frames)
Minimum Library (3-frame
with right and left media
b
frames)
c
Drive frame
Media frame
Bulk TAP frame
5/12 VDC power supply
24 VDC power supply
RIM
LTO-8 Fibre Channel
Full-Height
LTO-8 Fibre Channel or SAS
Half-Height
LTO-7 Fibre Channel
Full-Height
LTO-7 Fibre Channel or SAS
Half-Height
LTO-6 Fibre Channel
LTO-5, Fibre Channel
LTO-4, Fibre Channel
TS1160 technology
Power Consumption
(watts)
613
423
Estimated
153
30
21
33
29
12
Read/write: 40
d
Idle: 15
Read/write: 43
c
Idle: 14
Read/write: 31
c
Idle: 20
Read/write: 31
c
Idle: 20
Read/write: 28
c
Idle: 8
Read/write: 37
c
Idle: 19
Read/write: 37
c
Idle: 17.5
Read/write: 67
c
Idle: 35
User Guide—Spectra TFinity Library
Power Specifications
Heat Load, Continuous
(BTU/hour)
2093
1750
522
102
72
113
99
41
Read/write: 136
Read/write: 164
Read/write: 106
Read/write: 106
Read/write: 95
Read/write: 126
Read/write: 123
Read/write: 229
537