Chapter 13 — Drive Troubleshooting
Code
DLM
Health
Icon
7
8
9
November 2020
Cause and Solution
High probability of media error. An error occurred because of a faulty tape 
cartridge.
 Ensure the tape cartridge is the correct media type: 
 See LTO Read/Write Compatibility on page 550 for information about which 
media is compatible with each LTO drive generation. 
 Drive will not accept an expired cleaning cartridge.
 Drive will not accept a WORM cartridge when running diagnostic tests in 
Maintenance Mode. 
 Drive will not write over existing data sets on a WORM cartridge. Ensure 
you are appending data sets on WORM media rather than attempting to 
write over existing data sets.
 If another drive is available, insert the cartridge into the other drive and retry 
the operation.
 If the operation fails, discard the defective cartridge.
 If the operation succeeds, use the Drive Health Verification wizard to test 
the original drive (see Using DLM to Test a Drive on page 430).
 If the drive fails the DLM drive test, contact Spectra Logic Technical Support 
(see Contacting Spectra Logic on page 7).
 If the diagnostics succeed, the error was temporary.
 If another drive is not available, use the Drive Health Verification wizard to 
test the drive.
 If the drive fails the DLM drive test, contact Spectra Logic Technical 
Support.
 If the drive passes the DLM drive test, retry the operation to determine 
whether the error was temporary. If the operation fails again, discard the 
cartridge.
Note:
The error code clears when you reset of power cycle the drive or when 
you place it in maintenance mode.
SCSI interface or Fibre Channel failure.
A failure occurred in the drive hardware or in the SCSI bus. The error code clears 
after 10 seconds if the error does not recur. If the error persists, contact Spectra 
Logic Technical Support (see Contacting Spectra Logic on page 7).
RS‐422 error.
The drive determined that a drive interface or library interface failure occurred. 
The error code clears after 10 seconds if the error does not recur. If the error 
persists, contact Spectra Logic Technical Support (see Contacting Spectra Logic 
on page 7).
Interpret the Detailed Drive Information
User Guide—Spectra TFinity Library
423