D.2 UL and CSA Standards
n
L1-02: Motor Overload Protection Time
Setting Range: 0.1 to 5.0 min
Factory Default: 1.0 min
Parameter L1-02 determines how long the motor is allowed to operate before the oL1 fault occurs when the drive is running
a hot motor at 60 Hz and at 150% of the full load amp rating (E2-01) of the motor. Adjusting the value of L1-02 can shift the
set of oL1 curves up the y axis of the diagram below, but will not change the shape of the curves.
u
Precautionary Notes on External Heatsink (IP00/Open Type Enclosure)
When using an external heatsink, UL compliance requires covering exposed capacitors in the main circuit to prevent injury
to surrounding personnel.
The portion of the external heatsink that projects out can be protected with the enclosure or with the appropriate capacitor
cover after completing drive installation. Use
covers from a Yaskawa representative or directly from the Yaskawa sales department.
Drive Model
2A0110
2A0138
2A0169
2A0211
2A0250
2A0312
2A0360
2A0415
4A0058
4A0072
4A0088
4A0103
4A0139
4A0165
4A0208
4A0250
4A0296
4A0362
4A0414
4A0515
4A0675
504
Operation time (minutes)
10
7
3
1
0.4
0.1
0
100
Figure D.8 Motor Overload Protection Time
Table D.9
Table D.9 Capacitor Cover
Cold start
(characteristics when an
overload occurs at a
complete stop)
Hot start
(characteristics when an
overload occurs during
continuous operation at 100%)
Motor current (%)
150
200
E2-01 = 100% motor current
to match drive models with available capacitor covers. Order capacitor
Code Number
100-061-273
100-061-274
100-061-275
100-061-277
100-061-278
100-061-273
100-061-274
100-061-276
100-061-275
100-061-277
100-061-278
100-061-279
100-061-280
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual