Low City or Low Suction Inlet Pressure
This function is used with low suction inlet pressure switches on pressure booster systems for buildings that get their main
water supply from a municipality. This pressure switch enables and disables the pump system when the inlet supply is at a
low demand and when running the pump system in this condition will cause damage.
An inlet pressure switch is wired directly into the drive using one of the digital input terminals. If the pressure switch is active
and sufficient pressure is available, the drive system will operate normally. If the pressure switch indicates that incoming
pressure is too low, the drive will take the following actions:
• The drive will be forced into a sleep-like state (coast to stop).
• Any drives staged in multiplex mode will immediately coast to stop.
• The selected alarm "Low City Pressure", "Low Suction Pressure", or "Low Water In Tank" will be displayed (determined
by P4-24).
All drives will restart when sufficient pressure returns.
n
Required Control Wiring
Any one of the multi-function digital inputs (S1 to S8) must be wired and programmed with a low suction inlet pressure switch.
The appropriate terminal parameter (H1-oo) must be to set 73 (Low City Pressure). The action of the switch (normally open /
normally closed) is set in parameter P4-21.
n
Start Up Procedure
1.
Set all other parameters required for the application such as PI control loop, sleep, motor, and I/O parameters.
2.
Set one digital input for the low suction inlet pressure switch (H1-oo = 73). Wire the switch to this terminal.
3.
Configure the terminal for a normally open / closed switch type using parameter P4-21.
4.
Configure the delay times for activating and removing the alarm in parameters P4-23 and P4-24. This can be used to
stop the drive from cycling too frequently if the pressure varies a lot.
5.
Select the alarm message that will be displayed when a Low City condition is detected using parameter P4-24. Options
include "Low Cty Pressure", "Low Suction Pres", and "Low Watr In Tank".
n
Related Parameters, Faults, and Alarms
No.
P4-21
Low City Input Select
P4-22
Low City On-Delay Time
P4-23
Low City Off-Delay Time
P4-24
Low City Alarm Text
H1-oo
Function
Setting
73
Low City Press
HOA Keypad Display
Low City Pressure
Cause
Insufficient pressure is present on the inlet
to the pump.
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual
Parameter Name
H1 Multi-Function Digital Input Settings
Indicates that sufficient or insufficient pressure is present on the inlet to the pump. Used mainly for pressure
booster situations.
Low City Pressure
• Check pressure switch contact for correct operation.
• Check control wiring to drive terminal strip from pressure switch contact.
• Check to make sure that suction pressure is present by means of a separate measuring device.
4.6 iQpump Presets and Functions
Setting Values
Default: 1
Range: 0, 1
Default: 10 s
Minimum: 1
Maximum: 1000
Default: 5 s
Minimum: 0
Maximum: 1000
Default: 0
Range: 0 to 2
Description
Minor Fault Name
Possible Solution
4
165