B.12 P: Pump Parameters
No.
(Addr.
Name
Hex)
P3-11
(0CD2) Setpoint Boost after De-
Stage Time
P3-12
Multi Pump Setpoint
(0CD3)
Increase during
Transition
P3-13
Multi Pump Setpoint
(0CD4)
Decrease during
Transition
P3-14
(0CD5) Multiplex Stabilization
Time
P3-15
High Feedback Quick
(0CD6)
De-stage
<2>
P3-16
Low Feedback Quick
(0CD7)
De-stage
<2>
P3-30
Stage Selection Mode
(0CE5)
P3-31
De-Stage Selection
(0CE6)
Mode
P3-40
Pre-Charge Lag Pump
(0CEF)
Select
P3-41
Pre-Charge Lag Pump
(0CF0)
Run Time
P3-42
Post-Pre-Charge Lag
(0CF1)
Pump Operation
P3-43
Pre-Charge Lag Pump
(0CF2)
Delay Time
P3-50
(0CF9) Pump 2 Frequency
Shutdown Level
408
LCD Display
Sets the amount of time that the setpoint will remain boosted
after lag pump is de-staged.
SP Boost Time
Sets the system setpoint increase each time a new pump is
brought online.
MP Setpoint Inc
Pump 1: Setpoint
Pump 1 + 2: Setpoint + P3-12
Pump 1 + 2 + 3: Setpoint + 2 x P3-12
Sets the system setpoint decrease each time a new pump is
brought online.
MP Setpoint Dec
Pump 1: Setpoint
Pump 1 + 2: Setpoint - P3-13
Pump 1 + 2 + 3: Setpoint - 2 x P3-13
Sets the time used to stabilize the system when a pump is added
or shut down during multiplex operation.
When a pump is added, the stabilize timer temporarily disables
the lead/lag functionality for the programmed time to prevent
M-Stabilize Time
pump cycling.
Function is active in contactor multiplex mode (P1-01 = 1).
Time pump protection and lead/lag control is suspended during
stabilization time.
Sets the High Feedback level that will trigger a quick de-stage.
High FB De-stage
The quick de-stage uses an internal 2 sec delay.
A setting of 0 disables this feature.
Sets the Low Feedback level that will trigger a quick de-stage.
Low FB De-stage
The quick de-stage uses an internal 2 sec delay.
A setting of 0 disables this feature.
Stage Sel Mode
Sets the method of staging for the pumps.
0: Sequential
0: Sequential
1: Stop History
1: Stop history
Destage Sel Mode
Sets the method for removing contactor pumps.
0: LastInFirstOut
0: Last in, first out (LIFO)
1: FirstInFirstOut
1: First in, first out (FIFO)
Precharge LagSel
Selects which of the lag pumps can come on during a pre-charge.
0: Disabled
0: Disabled
2: Pump 2 (H2-0o = 80)
2: Pump2 (H2-0X=80)
3: Pump3 (H2-0X=81)
3: Pump 3 (H2-0o = 81)
4: Pump4 (H2-0X=82)
4: Pump 4 (H2-0o = 82)
5: Pump5 (H2-0X=83)
5: Pump 5 (H2-0o = 83)
6: Pump6 (H2-0X=84)
6: Pump 6 (H2-0o = 84)
Sets the length of time that the lag pump specified in P3-40 is
Precharge Lag Tm
energized.
Determines whether the lag pump set in pre-charge (P3-40)
Post PreChg Lag
turns off or maintains its state when pre-charge is completed.
0: Turn Off
0: Turn off
1: Continue
1: Continue
Sets the length of time that the drive is in the pre-charge mode
PreChg Lag Delay
before the lag pump set in P3-40 is energized.
Sets the level used for the multiplex pumping operation.
Parameter is active only when P3-02 is set to 0 or 2.
When P3-02 is set to 0 and a total of two pumps are running, the
last pump (Pump 2) that was brought online will be shut down
by opening the dedicated mult-function discrete output
(H2-0o = 80 to 84) when the output frequency falls below the
P2 Shutdown Freq
level set in this parameter for the time set in P3-09.
When P3-02 is set to 2 and a total of two pumps are running, the
last pump (Pump 2) that was brought online will be shut down
by opening the dedicated mult-function discrete output
(H2-0o = 80 to 84) when the delta feedback (setpoint minus
feedback) has exceeded the level programmed in this parameter
for the time set in P3-09.
Description
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual
Values
Page
Default: 5.0 s
Min.: 0.0
Max.: 60.0
Default: 0.0 PSI
<1>
Min.: 0.0
Max.: 6000.0
Default: 0.0 PSI
<1>
Min.: 0.0
Max.: 6000.0
Default: 2 s
Min.: 0
Max.: 3600
Default: 0.0 PSI
<1>
Min.: 0.0
Max.: 6000.0
Default: 0.0 PSI
<1>
Min.: 0.0
Max.: 6000.0
Default: 0
Range: 0, 1
Default: 0
Range: 0, 1
Default: 0
Range: 0; 2 to 6
Default: 0.0 min
Min.: 0.0
Max.: 3600.0
Default: 0
Range: 0, 1
Default: 2.0 min
Min.: 0.0
Max.: 600.0
Default: 40.0 Hz
Min.: 0.0
234
Max.: 400.0