YASKAWA iQpump1000 User Manual page 404

Ac drive intelligent pump controller
Hide thumbs Also See for iQpump1000:
Table of Contents

Advertisement

B.12 P: Pump Parameters
No.
(Addr.
Name
Hex)
P1-22
Loss of Prime Selection
(0C15)
Loss of Prime
P1-23
Maximum Restart Time
(0C16)
after Fault
P1-24
(0C17)
Level at Full Speed
<6>
P1-30
Low Water Digital Input
(0C1D)
Configuration
P1-31
High Water Digital
(0C1E)
Input Configuration
P1-32
System Units Custom
(0C1F)
1st Character
<6>
P1-33
System Units Custom
(0C20)
2nd Character
<6>
P1-34
System Units Custom
(0C21)
3rd Character
<6>
P1-40
(0C27)
Maximum Pump Speed Max Pump Speed
<10>
<1> Available in drive software versions PRG: 8554 and later. Not available in drive models 4A0930 and 4A1200.
<2> System units are set by P6-04, Water Flow Units. The PID Feedback is re-routed to come from the flow meter, pulse input (H6-01 = 5), or analog
(H3-0o = 22).
<3> Unit text is set by P1-02, System Units.
<4> Unit range and resolution are determined by P1-07, Minimum Pump Speed Units. Setting P1-07 to 1 (RPM) will set a default value of 900 RPM
(VTC) and 2400 RPM (all others). Setting P1-07 to 0 (Hz, default) will set a default value of 40.0 Hz.
<5> Unit text is set by P1-18, Prime Loss Detection Method.
<6> Available in drive software versions PRG: 8551 and later.
<7> Range is 0.0 to 999.9 with sign-bit "-" or "+" indicating Delta to Setpoint. Range is -999.9 to 999.9 in drive software versions PRG: 8551 and
earlier.
<8> Range is 0.0 to 999.9 with sign-bit "-" indicating Delta to Setpoint. Range is 0.0 to 6000.0 in drive software versions PRG: 8551 and earlier.
<9> Range is 0.0 to 999.9 with sign-bit "+" indicating Delta to Setpoint. Range is 0.0 to 6000.0 in drive software versions PRG: 8551 and earlier.
<10> Available in drive software versions PRG: 8552 and later. Not available in drive models 4A0930 and 4A1200.
404
LCD Display
Sets the drive response method during the "Loss of Prime"
Prime Loss Sel
condition.
0: Fault
0: Fault
1: Alarm
1: Alarm
2: Digital Output
2: Digital out only
Sets the time in minutes that the drive will wait before
LOP Max Rstrt T
attempting another restart when the restart fails or is not
attempted due to a continuing fault condition.
When set greater than 0, this level is used to override the P-gain
and I-limit with a calculated value based on Sleep level, Wake-
Level @ Full Spd
up level, Minimum Pump Speed, Transducer Scaling, and
Maximum Frequency.
This feature is disabled when set to 0.
Low Water DI Sel
Selects the configuration of the low water level digital input.
0: Normally Open
0: Normally open
1: Normally Closed
1: Normally closed
HighWater DI Sel
Selects the configuration of the high water level digital input.
0: Normally Open
0: Normally open
1: Normally Closed
1: Normally closed
Sets the first character of the custom unit display when P1-02 =
Sys Unit Custom1
26.
Sets the second character of the custom unit display when P1-02
Sys Unit Custom2
= 26.
Sets the third character of the custom unit display when P1-02
Sys Unit Custom3
= 26.
Sets the maximum pump speed.
This parameter does not affect operation when set to 0.0 or when
set to a value higher than E1-04 x d2-01.
This parameter is internally lower limited to the minimum pump
speed (P1-06, P4-12, d2-02) when not set to 0.0.
Description
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual
Values
Page
Default: 0
Range: 0 to 2
Default: 0.2 min
Min.: 0.2
Max.: 6000.0
Default: 0.0
Min.: 0.0
Max.: 6000.0
Default: 0
Range: 0, 1
Default: 0
Range: 0, 1
Default: 41
Min.: 20
Max.: 7A
Default: 41
Min.: 20
Max.: 7A
Default: 41
Min.: 20
Max.: 7A
Default: 0.0 Hz
Min.: 0.0
233
Max.: 440.0