YASKAWA iQpump1000 User Manual page 419

Ac drive intelligent pump controller
Hide thumbs Also See for iQpump1000:
Table of Contents

Advertisement

No.
(Addr.
Name
Hex)
P9-12
(0DFF) Remove Pump Mode
P9-13
Remove Frequency
(0E00)
Level
P9-14
(0E01)
Remove Delta Level
P9-15
(0E02)
Remove Delay Time
P9-16
(0E03)
Stabilization Time
P9-17
(0E04)
Setpoint Modifier
P9-18
High Feedback Quick
(0E05)
De-Stage
P9-19
(0E06)
Alternation Unit
P9-20
Allow Network Run
(0E07)
P9-21
(0E08)
Run Priority
P9-22
(0E09)
System Fault Retry
P9-23
Maximum Number of
(0E0A)
Running Pumps
P9-24
(0E0B) Lead Swap at Sleep
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual
LCD Display
Sets the detection method for de-staging to the previous lead
Remove Pump Mode
pump.
0: Output Frequency
0: Output frequency
1: Feedback
1: Feedback
2: Feedback + Fout
2: Feedback + Fout
3: Flow Meter
3: Flow meter
When P9-12 is set to 0, this parameter sets the level below which
the output frequency must fall for the time set in P9-15 before
the lead drive will send a request to be removed from the system
via the iQPump MEMOBUS network.
Remove Freq Lvl
When P9-12 is set to 2 and the delta feedback (feedback minus
setpoint) has exceeded the level set in P9-14 for the time set in
P9-15, this parameter sets the level below which the output
frequency must fall before the lead drive will request to be
removed from the system via the iQPump MEMOBUS network.
When P9-12 is set to 1, this parameter sets the level above which
the delta feedback (feedback minus setpoint) must rise for the
time set in P9-15 before the lead drive will request to be removed
from the system via the iQPump MEMOBUS network.
When P9-12 is set to 2 and the output frequency has exceeded
Remove Delta Lvl
the level set in P9-13 for the time set in P9-15, this parameter
sets the level above which the delta feedback (feedback minus
setpoint) frequency must rise before the lead drive will request
to be removed from the system via the iQPump MEMOBUS
network.
Sets the delay time before the lead drive is removed from the
system.
Remove Dly Time
Sets the time used top stabilize the system when a pump is staged
or de-staged.
Stabilize Time
Lead/lag control and pump protection are suspended during this
time.
Sets the value by which the system setpoint is incremented
depending on the number of pumps that are running.
Set-pt Modifier
Pump 1: Setpoint
Pump 2: Setpoint + ((X-1) (P9-17))
Sets the feedback level that will trigger a quick de-stage. Set as
a percentage of the P1-09 value.
High FB De-stage
The quick de-stage ignores parameters P9-12 to P9-15 and uses
an internal 2 second delay.
Setting this parameter to 0.0 disables the feature.
Sets the units used in P9-03.
Alternation Unit
0: Hours (H)
0: Hours (H)
1: Minutes (min)
1: Minutes (min)
Allow Net Run
Specifies when a network Run command is allowed.
0: Always
0: Always
1: First/Altrnation
1: First/alternation
2: First Only
2: First only
3: Alternation Only
3: Alternation only
Sets the lead drive selection priority overriding the P9-01
selection.
Run Priority
If multiple drives have the lowest P9-21 value, then P9-01
determines which drive becomes the lead.
Sets the number of times that the iQPump MEMOBUS network
will allow automatic restarts of system faults.
System Flt Retry
The drive uses L5-04, Fault Reset Interval Time, to determine
when to attempt a system fault restart.
Set this parameter to the same value for all drives on the network.
Sets the maximum number of pumps that can run on the system. Default: 8
MaxPumps Running
Sets the length of time for which the lead drive will be in Sleep
Mode before this drive will request a swap when there is another
Lead Swap @Sleep
drive available with a lower P9-21 setting.
Setting this parameter to 0 will disable the function.
B.12 P: Pump Parameters
Description
Values
Page
Default: 0
Range: 0 to 3
Default: 40.0 Hz
Min.: 0.0
Max.: 400.0
Default: 0.0 PSI
<1>
Min.: 0.0
Max.: 6000.0
Default: 10 s
Min.: 0
Max.: 3600
Default: 3 s
Min.: 0
Max.: 3600
Default: 0.0 PSI
<1>
Min.: -999.9
Max.: 999.9
Default: 97.0%
Min.: 0.0
Max.: 100.0
Default: 0
Range: 0, 1
Default: 0
Range: 0 to 3
Default: 8
Min.: 1
Max.: 16
Default: 5
Min.: 0
Max.: 10
Min.: 1
Max.: 8
B
Default: 0 s
Min.: 0
Max.: 7200
419