YASKAWA iQpump1000 User Manual page 385

Ac drive intelligent pump controller
Hide thumbs Also See for iQpump1000:
Table of Contents

Advertisement

H3-oo
Function
Setting
Regenerative torque
12
limit
15
General torque limit
Differential PID
16
feedback
1F
Through mode
HAND Frequency
20
Reference
Geothermal
21
Temperature
22
Flow Meter
Water Level or Suction
23
Input
24
PI Feedback Backup
<1>
25
Secondary PI Setpoint
26
Secondary PI Feedback PI2 Feedback
27
PI Auxiliary Feedback
<4>
Level
28
Differential PI
<4>
Feedback
<1> Available in drive software versions PRG: 8551 and later.
<2> When Pressure Control is enabled (Q5-01 = 1), the action of the analog input is normal. A higher voltage or current on the input causes a higher
pressure to be read in the drive.
<3> When Vacuum Control is enabled (Q5-01 = 2), the action of the analog input is reversed. A higher voltage or current on the input causes a lower
pressure (or higher level of vacuum) to be read in the drive.
<4> Available in drive software versions PRG: 8552 and later. Not available in drive models 4A0930 and 4A1200.
u
H4: Analog Outputs
No.
(Addr.
Name
Hex)
Multi-Function Analog
H4-01
Output Terminal FM
(041D)
Monitor Selection
H4-02
Multi-Function Analog
(041E)
Output Terminal FM
Gain
H4-03
Multi-Function Analog
(041F)
Output Terminal FM
Bias
Multi-Function Analog
H4-04
Output Terminal AM
(0420)
Monitor Selection
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual
H3 Multi-Function Analog Input Settings
LCD Display
OLV
OLV
OLV
OLV
Regen Torq Limit
10 V = Motor rated torque
OLV
OLV
OLV
OLV
Torque Limit
10 V = Motor rated torque
10 V = 100%
PID Feedback 2
Not Used
Set this value when using the terminal in the pass-through mode.
Hand Freq. Ref.
Full scale: Max. frequency (E1-04)
Full scale: Q2-02 = 10 V (or 20 mA), Q2-01 = 0 V (or 4 mA)
Geothermal Temp
This input is internally limited to -110.0 °F to +320.0 °F after gain and bias.
Flow Meter
Full scale: P6-01
When Water Level Control is enabled (Q4-01 = 1):
0 V or 4 mA = 0 (ft)
10 V or 20 mA = Q4-02 (PSI) * 2.308 ft/PSI OR
When Suction Pressure Control is enabled (Q5-01 = 1)
WaterLvl/Suction
0 V or 4 mA = 9 (PSI)
10 V or 20 mA = Q5-02 (PSI) OR
When Vacuum Control is enabled (Q5-01 = 2)
0 V or 4 mA = 0 ("Hg)
10 V or 20 mA = Q5-02 ("Hg)
PI FdBack Backup
Full scale: FB Device Scaling (P1-03)
PI2 Setpoint
10 V = S3-02 (maximum output frequency)
10 V = S3-02 (maximum output frequency)
0 V or 4 mA = 0 (unit based on Q6-22)
PI Aux FB Level
10 V or 2 0mA = Q6-02 (unit based on Q6-22)
Diff PI Feedback
Full scale: FB Device Scaling (P1-03)
LCD Display
Selects the data to be output through multi-function analog
output terminal FM.
Term FM FuncSel
Set the desired monitor parameter to the digits available in
Uo-oo.
For example, enter "103" for U1-03.
Sets the signal level at terminal FM that is equal to 100% of the
selected monitor value.
Terminal FM Gain
Sets the signal level at terminal FM that is equal to 0% of the
selected monitor value.
Terminal FM Bias
Selects the data to be output through multi-function analog
output terminal AM.
Terminal AM Sel
Set the desired monitor parameter to the digits available in
Uo-oo.
For example, enter "103" for U1-03.
B.8 H Parameters: Multi-Function Terminals
Description
<2>
<3>
Description
Page
Values
Page
Default: 102
Range: 000 to
227
999
Default: 100.0%
Min.: -999.9
228
Max.: 999.9
Default: 0.0%
Min.: -999.9
228
Max.: 999.9
Default: 103
B
Range: 000 to
227
999
385