u
Terminal AM/FM Signal Selection
The signal type for terminals AM and FM can be set to either voltage or current output using jumper S5 on the terminal board
as explained in
Table
3.15. When changing the setting of jumper S5, parameters H4-07 and H4-08 must be set accordingly.
The default selection is voltage output for both terminals.
Terminal
Terminal AM
Terminal FM
No.
Parameter Name
H4-07 Terminal FM signal level selection
H4-08 Terminal AM signal level selection
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual
Table 3.15 Jumper S5 Settings
Voltage Output
V
I
FM
AM
V
I
FM
AM
Table 3.16 Parameter H4-07 and H4-08 Details
Description
0: 0 to 10 Vdc
1: -10 to 10 Vdc
2: 4 to 20 mA
3.9 Control I/O Connections
Current Output
V
I
FM
AM
V
I
FM
AM
Setting Range
Default Setting
0 to 2
0
3
129