YASKAWA iQpump1000 User Manual page 435

Ac drive intelligent pump controller
Hide thumbs Also See for iQpump1000:
Table of Contents

Advertisement

No.
(Addr.
Name
Hex)
S3-11
Secondary PI Output
(3224)
Level Selection
S3-12
Secondary PI Disable
(3225)
Mode
S3-13
Secondary PI Low
(3226)
Feedback Detection
Level
S3-14
Secondary PI Low
(3227)
Feedback Detection
Time
S3-15
Secondary PI High
(3228)
Feedback Level
S3-16
Secondary PI High
(3229)
Feedback Detection
Time
S3-17
(322A) Secondary PI Feedback
Detection Selection
<1> Unit is determined by S3-04.
<2> Upper limit is S3-02, decimal placeholder is determined by S3-03.
u
S6: Protection
No.
(Addr.
Name
Hex)
S6-01
Emergency Override
(3236)
Speed
S6-02
Emergency Override
(3237)
Reference Selection
Output Phase Loss
S6-07
Level for Dynamic
(323C)
Noise Control
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual
LCD Display
Sets the secondary PI controller output direction.
PI2 Out Lvl Sel
0: Normal Output (direct acting)
0: Direct Acting
1: Inverse Output (inverse acting)
1: Inverse Acting
PI2 Disable Mode
Selects the secondary PI controller output when disabled.
0: No output
0: No output (0%)
1: Lower Limit
1: Lower Limit (S3-10)
2: Setpoint
2: Setpoint
Sets the secondary PI low feedback detection level.
PI2 Low FB Lvl
Sets the secondary PI low feedback detection delay time in
seconds.
PI2 Low FB Time
Sets the secondary PI high feedback detection level.
PI2 High FB Lvl
Sets the secondary PI high feedback detection delay time in
seconds.
PI2 High FB Tim
Selects when secondary PI controller low and high feedback
PI2 FB Det Sel
detection are active.
0: PI2 Enabled
0: Secondary PI enabled
1: Always
1: Always
LCD Display
Sets the speed command used in emergency override mode
E Override Speed
when S6-02 = 0.
E OverrideRefSel
Selects the emergency override speed source.
0: Use S6-01 Ref
0: Use S6-01 Reference
1: Use Freq Ref
1: Use Frequency Reference
Reduces the output phase loss level when Dynamic Noise
DNC Outp Ph Loss
Control is active.
B.14 S: Special Application
Description
Description
Values
Page
Default: 0
Range: 0, 1
Default: 0
Range: 0 to 2
Default: 0.00
<1>
Min.: 0.00
Max.: 600.00
<2>
Default: 1.0 s
Min.: 0.0
Max.: 25.5
Default: 100.00
<1>
Min.: 0.00
Max.: 600.00
<2>
Default: 1.0 s
Min.: 0.0
Max.: 25.5
Default: 0
Range: 0, 1
Values
Page
Default: 0.00 Hz
Min.: 0.00
Max.: 400.00
Default: 0
Range: 0, 1
Default: 100.0%
Min.: 10.0
Max.: 100.0
B
435

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents