4.7 Basic iQpump Setup and Application Preset Parameters
n
E2-01: Motor Rated Current
Provides motor control, protects the motor, and calculates torque limits. Set E2-01 to the full load amps (FLA) stamped on
the motor nameplate. If Auto-Tuning completes successfully, the value entered to T1-04 will automatically be saved to E2-01.
No.
E2-01
<1> Display is in the following units:
2A0004 to 2A0040, 4A0002 to 4A0023, and 5A0007 to 5A0017: 0.01 A units.
2A0056 to 2A0415, 4A0031 to 4A0675, and 5A0022 to 5A0242: 0.1 A units.
4A0930 and 4A1200: 1 A units.
Note:
An oPE02 error will occur if E2-01 ≤ E2-03. Set E2-03 correctly to prevent this error.
n
E2-04: Number of Motor Poles
Set the number of motor poles to E2-04. If Auto-Tuning completes successfully, the value entered to T1-06 will automatically
be saved to E2-04.
No.
E2-04
n
H1-01 to H1-08: Functions for Terminals S1 to S8
These parameters assign functions to the multi-function digital inputs. The various functions and settings are listed in
4.21.
No.
H1-01
Multi-Function Digital Input Terminal S1 Function Selection
H1-02
Multi-Function Digital Input Terminal S2 Function Selection
H1-03
Multi-Function Digital Input Terminal S3 Function Selection
H1-04
Multi-Function Digital Input Terminal S4 Function Selection
H1-05
Multi-Function Digital Input Terminal S5 Function Selection
H1-06
Multi-Function Digital Input Terminal S6 Function Selection
H1-07
Multi-Function Digital Input Terminal S7 Function Selection
H1-08
Multi-Function Digital Input Terminal S8 Function Selection
<1> Number appearing in parenthesis is the default value after performing a 3-Wire initialization (A1-03 = 3330).
Setting
0
3-Wire sequence
2
External Reference 1/2 Selection
3
Multi-Step Speed Reference 1
222
Accel Time 1
(C1-01)
Output
frequency
FWD (REV)
Run command
Accel/Decel Time Selection 1
(Terminals S1 to S8, H1- oo = "7")
Figure 4.41 Timing Diagram of Accel/Decel Time Change
Parameter Name
Motor Rated Current
Parameter Name
Number of Motor Poles
Parameter Name
Table 4.21 Multi-Function Digital Input Terminal Settings
Function
Decel Time 1
Decel Time 2
(C1-02)
(C1-04)
Accel Time 2
(C1-03)
Decel Time 1
(C1-02)
Time
ON
OFF
ON
ON
OFF
Setting
Range
1 to 9F
40 (F)
1 to 9F
F: Through Mode
0 to 9F
26: External Pump Fault
0 to 9F
14: Fault Reset
0 to 9F
8D (0)
0 to 9F
80 (3)
0 to 9F
81 (4)
0 to 9F
F (6)
Page
Setting
4
Multi-Step Speed Reference 2
5
Multi-Step Speed Reference 3
6
Jog reference selection
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual
Setting Range
10% to 200% of the drive
<1>
rated current
Setting Range
2 to 48
Default
<1>
: Forward Run Command (2-Wire sequence)
<1>
: Multi Setpoint 1
<1>
: HAND Mode
<1>
: HAND Mode 2
<1>
: Through Mode
Function
Default
Determined by
o2-04
Default
2
Table
Page

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents