YASKAWA iQpump1000 User Manual page 392

Ac drive intelligent pump controller
Hide thumbs Also See for iQpump1000:
Table of Contents

Advertisement

B.9 L: Protection Function
No.
(Addr.
Name
Hex)
L4-04
Speed Agreement
(049C)
Detection Width (+/-)
Frequency Reference
L4-05
Loss Detection
(049D)
Selection
L4-06
Frequency Reference at
(04C2)
Reference Loss
L4-07
Speed Agreement
(0470)
Detection Selection
u
L5: Fault Restart
No.
(Addr.
Name
Hex)
L5-01
Number of Auto Restart
(049E)
Attempts
Auto Restart Fault
L5-02
Output Operation
(049F)
Selection
L5-04
Fault Reset Interval
(046C)
Time
L5-40
Low Feedback Fault
(0670)
Retry Selection
L5-41
High Feedback Fault
(0671)
Retry Selection
L5-42
Feedback Loss Fault
(0672)
Retry Selection
L5-50
Setpoint Not Met Retry
(067A)
Selection
L5-51
Loss of Prime Fault
(067B)
Retry Selection
L5-52
Pump Over Cycle Fault
(067C)
Retry Selection
L5-53
Volute-TStat Retry
(067D)
Selection
392
LCD Display
L4-04 sets the hysteresis or allowable margin for speed
Spd Agree Wdth+-
detection.
Ref Loss Sel
0: Stop. Drive stops when the frequency reference is lost.
0: Stop
1: Run. Drive runs at a reduced speed when the frequency
1:
reference is lost.
Run@L4-06PrevRef
Sets the percentage of the frequency reference that the drive
Fref at Floss
should run with when the frequency reference is lost.
Freq Detect Sel
0: No detection during baseblock.
0: No Detection @BB
1: Detection always enabled.
1: Always Detected
LCD Display
Sets the number of times the drive may attempt to restart after
Num of Restarts
the following faults occur: GF, LF, oC, ov, PF, rH, rr, oL1, oL2,
oL3, oL4, STo, Uv1.
Restart Sel
0: Fault output not active.
0: Flt Outp Disabld
1: Fault output active during restart attempt.
1: Flt Outp Enabled
Sets the amount of time to wait between performing fault
Flt Reset Wait T
restarts.
Determines whether the LFB-Low Feedback fault can be auto-
Low Feedback
restarted.
0: No retry
0: No retry
1: Retry
1: Retry
Determines whether the HFB-High Feedback fault can be auto-
High Feedback
restarted.
0: No retry
0: No retry
1: Retry
1: Retry
Determines whether the FDBKL-Wire Break fault can be auto-
Feedback Loss
restarted.
0: No retry
0: No retry
1: Retry
1: Retry
Determines whether the NMS-Setpoint not Met fault can be
SetPoint Not Met
auto-restarted.
0: No retry
0: No retry
1: Retry
1: Retry
Determines whether the LOP-Loss of Prime fault can be auto-
Loss of Prime
restarted.
0: No retry
0: No retry
1: Retry
1: Retry
Determines whether the POC-Pump Over Cycle fault can be
Pump Over Cycle
auto-restarted.
0: No retry
0: No retry
1: Retry
1: Retry
Determines whether the Volute T-Stat fault can be auto-
restarted.
0: No retry
Volute-TStat Flt
1: Retry
0: No retry
1: Retry
Note:
Description
Description
The drive will restart only after the Volute-Tstat
digital input deactivates and the L5-04 timer
expires.
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual
Values
Page
Default: 2.0
Min.: 0.0
Max.: 20.0
Default: 0
Range: 0, 1
Default: 80.0%
Min.: 0.0
Max.: 100.0
Default: 0
Range: 0, 1
Values
Page
Default: 5
Min.: 0
Max.: 10
Default: 0
Range: 0, 1
Default: 20.0 s
Min.: 10.0
Max.: 3600.0
Default: 0
Range: 0, 1
Default: 0
Range: 0, 1
Default: 0
Range: 0, 1
Default: 0
Range: 0, 1
Default: 0
Range: 0, 1
Default: 0
Range: 0, 1
Default: 0
Range: 0, 1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents