4.7 Basic iQpump Setup and Application Preset Parameters
When Q6-25 (PI Aux Control Activation Level) > 0, the PI Aux Feedback Level (H3-oo = 27) has to rise above the level
set in Q6-25 for the time set in Q6-26 (PI Aux Control Activation Delay) before the PI Aux Controller is allowed to affect the
output frequency.
When active, the PI Aux Feedback Level (H3-oo = 27) has to drop below the Q6-25 level for the time set in Q6-26 before
the PI Aux Controller is deactivated and not allowed to affect the output frequency.
Setting 1: Inverse Acting
When Q6-25 (PI Aux Control Activation Level) = 0, the PI Aux Controller can affect the output frequency if the controller's
output is less than the primary PID (System Pressure) controller's output.
When Q6-25 (PI Aux Control Activation Level) > 0, the PI Aux Feedback Level (H3-oo = 27) has to drop below the level
set in Q6-25 for the time set in Q6-26 (PI Aux Control Activation Delay) before the PI Aux Controller is allowed to affect the
output frequency.
When active, the PI Aux Feedback Level (H3-oo = 27) has to rise above the Q6-25 level for the time set in Q6-26 before
the PI Aux Controller is deactivated and not allowed to affect the output frequency.
The following are the selections available for custom system units:
Setting
Character
20
SPACE
21
!
22
"
23
#
24
$
25
%
26
&
27
'
28
(
29
)
2A
*
2B
+
2C
,
2D
-
2E
.
2F
/
30
0
31
1
32
2
33
3
n
S2-01/S2-06/S2-11/S2-16: Sequence Timers 1 to 4 Start Time
Sets the start times for timers 1 to 4.
If the Stop Time is set to a higher value than the Start Time, the Sequence Timers will be active starting from the set Start
Time, run through midnight, and stop the following day at the set Stop Time.
Note:
Setting the sequence timer start time to a higher value than the sequence timer stop time disables that sequence timer in drive software
versions PRG: 8551 and earlier.
No.
S2-01
S2-06
S2-11
S2-16
<1> Default is 00:00 and range is 00:00 to 24:00 when o4-20 is set to 1 (24-hour).
244
Setting
Character
34
4
35
5
36
6
37
7
38
8
39
9
41
A
42
B
43
C
44
D
45
E
46
F
47
G
48
H
49
I
4A
J
4B
K
4C
L
4D
M
4E
N
Name
Sequence Timer 1 Start Time
Sequence Timer 2 Start Time
Sequence Timer 3 Start Time
Sequence Timer 4 Start Time
Setting
Character
4F
O
50
P
51
Q
52
R
53
S
54
T
55
U
56
V
57
W
58
X
59
Y
5A
Z
61
a
62
b
63
c
64
d
68
e
66
f
67
g
68
h
Setting Range
12:00AM to 11:59PM
12:00AM to 11:59PM
12:00AM to 11:59PM
12:00AM to 11:59PM
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual
Setting
Character
69
I
6A
j
6B
k
6C
l
6D
m
6E
n
6F
o
70
p
71
q
72
r
73
s
74
t
75
u
76
v
77
w
78
x
79
y
7A
z
Default
<1>
<1>
12:00AM
<1>
<1>
12:00AM
<1>
<1>
12:00AM
<1>
<1>
12:00AM

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents