YASKAWA iQpump1000 User Manual page 307

Ac drive intelligent pump controller
Hide thumbs Also See for iQpump1000:
Table of Contents

Advertisement

4.
Disconnect all option cards and options, making sure they are intact before reusing.
5.
Replace the drive and wire the main circuit.
n
Installing the Drive
1.
After wiring the main circuit, connect the terminal block to the drive as shown in
to fasten the terminal block into place.
2.
Reconnect options for the new drive the same way the options were connected in the old drive. Connect option boards
to the same option ports in the new drive that were used in the old drive.
3.
Replace the terminal cover.
4.
After powering on the drive, all parameter settings are transferred from the terminal board to the drive memory. If an
oPE04 error occurs, load the parameter settings saved on the terminal board to the new drive by setting parameter
A1-03 to 5550. Reset the Maintenance Monitor function timers by setting parameters o4-01 through o4-12 to 0, and
parameter o4-13 to 1.
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual
Figure 6.3 Remove the Terminal Board
Figure 6.4 Disconnected Removable Terminal Board
Figure 6.5 Install the Terminal Board
6.3 Drive Replacement
Figure
6.5. Use the installation screw
6
307

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents