5.6 Copy Function Related Displays
Keypad Display
ndAT
Cause
The drive from which the parameters were copied
and the drive to which the parameters will be
written have different electrical specifications,
capacities, are set to different control modes, or are
different models.
The device being used to write the parameters is
blank and does not have any parameters saved on
it.
Keypad Display
rdEr
Cause
Failed while attempting to read parameter settings
from the drive.
Keypad Display
rEAd
Cause
Displayed while the parameter settings are being
read onto the USB Copy Unit.
Keypad Display
vAEr
Cause
The drive from which the parameters were copied
and the drive on which the Verify mode is being
performed have different electrical specifications
or are a different capacity.
Keypad Display
vFyE
Cause
Indicates that parameter settings that have been
Read and loaded onto the Copy Unit or HOA
keypad are different.
Keypad Display
vrFy
Cause
The Verify mode has confirmed that parameters
settings on the drive and parameters read to the
copy device are identical.
294
Model, Voltage Class, Capacity Mismatch
Make sure model numbers and specifications are the same for both drives.
Make sure all connections are correct, and copy the parameter settings onto the USB Copy Unit or
the HOA keypad.
Error Reading Data
Press and hold the READ key on the USB Copy Unit for at least one second to have the unit read
parameters from the drive.
Reading Parameter Settings (flashing)
This is not an error.
Voltage Class, Capacity Mismatch
Make sure electrical specifications and capacities are the same for both drives.
Parameter settings in the drive and those saved to the copy function are not the same
To synchronize parameters, either write the parameters saved on the USB Copy Unit or HOA keypad
onto the drive, or Read the parameter settings on the drive onto the USB Copy Unit.
Comparing Parameter Settings (flashing)
This is not an error.