YASKAWA iQpump1000 User Manual page 151

Ac drive intelligent pump controller
Hide thumbs Also See for iQpump1000:
Table of Contents

Advertisement

n
Related Parameters
No.
A1-01
Access Level Selection
A1-03
Initialize Parameters
E2-01
Motor Rated Current
E2-04
Number of Motor Poles
P1-03
Feedback Device Scaling
P1-11
High Feedback Level
P1-06
Minimum Pump Speed
P1-04
Start / Draw Down Level
P2-02
Sleep Level
P4-10
AUTO Mode Operator Run Power Down Storage
P5-02
HAND Speed Reference 1
P5-04
HAND Key Function Selection
Q1-01
PID Controller Setpoint 1
U1-99
Anti-No-Flow Timer
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual
Parameter Name
4.6 iQpump Presets and Functions
Setting Values
Default: 2
Range: 0 to 3
Default: 0
Range: 0 to 5550; 6008 to 6014; 7770, 7771
Default:
Min.: 10% of drive rated current
Max.: 200% of drive rated current
Default: 2
Min.: 2
Max.: 48
Default: 145.0 PSI
Min.: 0.1
Max.: 6000.0
Default: 0.0 PSI
Min.: 0.0
Max.: 6000.0
Default: 40.0 Hz
Min.: 0.0
Max.: [E1-04]
Default: 0.0
Min.: -999.9
Max.: 999.9
Default: 0.0 Hz
Min.: 0.0
Max.: 6000.0
Default: 0
Range: 0, 1
Default: 40.0 Hz
Min.: 0
Max.: [E1-04]
Default: 1
Range: 0, 1
Default: 0.0
Min.: 0.0
Max.: 6000.0
No signal output available
4
151

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents