YASKAWA iQpump1000 User Manual page 380

Ac drive intelligent pump controller
Hide thumbs Also See for iQpump1000:
Table of Contents

Advertisement

B.8 H Parameters: Multi-Function Terminals
H2-oo
Function
Setting
2
Speed agree 1
3
User-set speed agree 1
4
Frequency detection 1
5
Frequency detection 2
6
Drive ready
7
DC bus undervoltage
During baseblock
8
(N.O.)
Frequency reference
9
source
<1>
Run command source
A
<2>
HAND Mode
A
Torque detection 1
B
(N.O.)
Frequency reference
C
loss
D
Braking resistor fault
E
Fault
<1>
Through mode
F
10
Minor fault
Fault reset command
11
active
12
Timer output
13
Speed agree 2
14
User-set speed agree 2
15
Frequency detection 3
16
Frequency detection 4
Torque detection 1
17
(N.C.)
Torque detection 2
18
(N.O.)
Torque detection 2
19
(N.C.)
1A
During reverse
During baseblock
1B
(N.C.)
1E
Restart enabled
Motor overload alarm
1F
(oL1)
Drive overheat pre-
20
alarm (oH)
Mechanical weakening
22
detection
380
H2 Multi-Function Digital Output Settings
LCD Display
Closed: Output frequency equals the speed reference (plus or minus the hysteresis
Fref/Fout Agree1
set to L4-02).
Closed: Output frequency and speed reference equal L4-01 (plus or minus the
Fref/Set Agree 1
hysteresis set to L4-02).
Closed: Output frequency is less than or equal to the value in L4-01 with hysteresis
Freq Detect 1
determined by L4-02.
Closed: Output frequency is greater than or equal to the value in L4-01 with
Freq Detect 2
hysteresis determined by L4-02.
Drive Ready
Closed: Power up is complete and the drive is ready to accept a Run command.
DC Bus Undervolt
Closed: DC bus voltage is below the Uv trip level set in L2-05.
Closed: Drive has entered the baseblock state (no output voltage).
BaseBlk 1
Open: External Reference 1 or 2 supplies the frequency reference (set in b1-01 or
Ref Source
b1-15).
Closed: Digital operator supplies the frequency reference.
Open: External Reference 1 or 2 supplies the Run command (set in b1-02 or b1-16).
Run Cmd Source
Closed: Digital operator supplies the Run command.
Closed: Pump is in HAND Mode Operation
Hand Mode
Closed: An overtorque or undertorque situation has been detected.
Trq Det 1 N.O.
Closed: Analog frequency reference has been lost.
Loss of Ref
Frequency reference loss is detected when the frequency reference drops below
10% of the reference within 400 ms.
Closed: Braking resistor or transistor is overheated or faulted out.
DB Overheat
Note:
Fault
Closed: Fault occurred.
Set this value when using the terminal in the pass-through mode.
Not Used
Closed: An alarm has been triggered, or the IGBTs have reached 90% of their
Minor Fault
expected life span.
Closed: A command has been entered to clear a fault via the input terminals or
Reset Cmd Active
from the serial network.
Timer Output
Closed: Timer output.
Closed: When drive output frequency equals the frequency reference ±L4-04.
Fref/Fout Agree2
Note:
Fref/Set Agree 2
Closed: When the drive output frequency is equal to the value in L4-03 ±L4-04.
Closed: When the drive output frequency is less than or equal to the value in L4-03
Freq Detect 3
±L4-04.
Closed: When the output frequency is greater than or equal to the value in L4-03
Freq Detect 4
±L4-04.
Open: Overtorque or undertorque has been detected.
Trq Det 1 N.C.
Closed: Overtorque or undertorque has been detected.
Trq Det 2 N.O.
Open: Overtorque or undertorque has been detected.
Trq Det 2 N.C.
Reverse Dir
Closed: Drive is running in the reverse direction.
Open: Drive has entered the baseblock state (no output voltage).
BaseBlk 2
Dur Flt Restart
Closed: An automatic restart is performed
Closed: oL1 is at 90% of its trip point or greater. An oH3 situation also triggers
Overload (OL1)
this alarm.
Closed: Heatsink temperature exceeds the parameter L8-02 value.
OH Prealarm
Closed: Mechanical weakening detected.
MechFatigue(OL5)
Description
This setting is not available in models 4A0930 and 4A1200.
This setting is not available in models 4A0930 and 4A1200.