n
Related Parameters, Monitors, and Multi-Function Digital Output Settings
No.
P4-14
Two Motor Alternation Selection
P4-15
Two Motor Alternation Operation Selection
P4-16
Two Motor Alternation Time
U1-82
Two Motor Time to Alternate
H2-oo
Function
43
2 Motor Alternate
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual
Parameter Name
H2 Multi-Function Digital Output Settings
Open: Motor 1 in use (or 2-motor alternation is disabled)
Closed: Motor 2 in use
4.6 iQpump Presets and Functions
Setting Values
Default: 24.0 H
Range: 0.1 to 100.0 H
Full scale: N/A
Description
Default: 0
Range: 0 to 3
Default: 0
Range: 0, 1
4