u
MEMOBUS Multiplexing System-wide Parameter Entry
This function allows parameter changes to be pushed through the MEMOBUS Multiplex network.
Note:
1. This function is available in drive software versions PRG: 8552 and later.
2. Not available in drive models 4A0930 and 4A1200.
n
Network Parameter Push Operation
Parameter P9-98 enables and disables the network parameter push function.
When P9-98 is set to 0 (Disabled), changes to any parameter will only be written to the drive on which the parameter was
changed.
When P9-98 is set to 1 (Enabled/Prompt), changes to system-wide parameters display the prompt shown in
whether to write the change on the selected drive or to all the drives on the network.
Changes to non-system-wide parameters will only be written to the drive on which the parameter was changed.
System-Wide Parameters on page 192
MEMOBUS Multiplex network.
Selecting "Cancel" aborts the change.
Selecting "This Pump" causes the change to be written only on the drive on which the parameter was changed.
Selecting "System" attempts to write the change to the drive on which the parameter was changed and all other drives currently
online (The number of nodes is based on P9-25).
The operator displays a WAIT message as shown in
each node.
The drive will display the confirmation screen shown in
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual
for a list of non-system-wide parameters that cannot be pushed to other drives on the
Figure 4.25 Parameter Change Prompt
Figure 4.26
for 5 s while the MEMOBUS Multiplex network writes to
Figure 4.26 WAIT Message
Figure 4.28
4.6 iQpump Presets and Functions
after all drives have been accessed.
Figure 4.25