YASKAWA iQpump1000 User Manual page 427

Ac drive intelligent pump controller
Hide thumbs Also See for iQpump1000:
Table of Contents

Advertisement

No.
(Addr.
Name
Hex)
Q5-20
Suction Pressure Speed
(0F36)
Control
<3>
Q5-22
Suction Pressure
(0F38)
Decimal Place Position
<4>
Q5-25
Suction Pressure
(0F3B)
Control Activation
<4>
Level
Q5-26
Suction Pressure
(0F3C)
Control Activation/
<4>
Deactivation Delay
<1> Units are determined by Q5-01, Suction Pressure Select, setting.
<2> Units are determined by Q5-18, Suction Pressure Detection Time Unit, setting.
<3> Available in drive software versions PRG: 8552 and later. Not available in drive models 4A0930 and 4A1200.
<4> Available in drive software versions PRG: 8554 and later. Not available in drive models 4A0930 and 4A1200.
u
Q6: PI Auxiliary Control
No.
(Addr.
Name
Hex)
Q6-01
PI Auxiliary Control
(0F50)
Selection
<1>
Q6-02
(0F51)
PI Auxiliary Control
Feedback Scale
<1>
Q6-03
(0F52)
PI Auxiliary Control
Setpoint
<1>
Q6-04
(0F53)
PI Auxiliary Control
Minimum Level
<1>
Q6-05
(0F54)
PI Auxiliary Control
Sleep Delay Time
<1>
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual
LCD Display
Selects whether the Suction Pressure Controller has an effect on
SucPres Spd Ctrl
output speed.
0: Disabled
0: Disabled
1: Enabled
1: Enabled
Sets the number of decimal places for the Suction Pressure
Suc Press Dec Pt
parameters and monitor:
0: No Dec (XXXXX)
0: No Dec (XXXXX)
1: 1 Dec (XXXX.X)
1: 1 Dec (XXXX.X)
2: 2 Dec (XXX.XX)
2: 2 Dec (XXX.XX)
3: 3 Dec (XX.XXX)
3: 3 Dec (XX.XXX)
When the suction pressure drops below this level for more than
the Q5-26 time, Suction Pressure Control is activated allowing
it to affect the output frequency. When the suction pressure rises
above this level for more than the Q5-26 time, Suction Pressure
SucPress Act Lvl
is deactivated causing it to have no effect on the output
frequency.
Suction Pressure Control is always active (if enabled) when set
to 0.
When the suction pressure drops below the Q5-25 level for more
than this time, Suction Pressure Control is activated allowing it
to affect the output frequency. When the suction pressure rises
SucPress Act Dly
above the Q5-25 level for more than this time, Suction Pressure
Control is deactivated causing it to have no effect on the output
frequency.
LCD Display
PI Aux Ctrl Sel
Sets the mode of operation for the PI Auxiliary Control function.
0: Disabled
0: Disabled
1: Enabled
1: Enabled
Sets the full scale (10 V or 20 mA) output of the pressure
PI Aux Lvl Scale
transducer connected to the analog input terminal programmed
for "PI Aux FB Level" (H3-oo = 27).
Sets the level to which the drive will attempt to regulate.
PI Aux Setpoint
Sets the level below which the drive must fall for longer than
the time set in Q6-05 time before the drive goes to sleep and
PI Aux Min Lvl
turns off all lag pumps.
Note:
Inverse Acting (Q6-23 = 1): Sets the amount of time that the
drive will delay before going to sleep after the level drops below
Q6-04 setting.
Sleep Dly Time
Normal Acting (Q6-23 = 0): Sets the amount of time that the
drive will delay before going to sleep after the level rises above
Q6-24 setting Range: 0 to 3600 s Default 5 s
B.13 Q: PID Controller Parameters
Description
Description
This feature is disabled when set to 0.0.
Values
Page
Default: 1
Range: 0, 1
Default: 1
Range: 0 to 3
Default: 10.0
PSI
Range: 0.0 to
<1>
1200.0
Default: 2 s
Range: 0 to
3600
Values
Page
Default: 0
Range: 0, 1
Default: 145.0
<3>
PSI
Min.: 1.0
Max.: 6000.0
Default: 20.0
<3>
PSI
Min.: 0.0
Max.: 6000.0
Default: 10.0
<3>
PSI
Min.: 0.0
Max.: 6000.0
Default: 5 s
Min.: 0
Max.: 3600
B
427