YASKAWA iQpump1000 User Manual page 354

Ac drive intelligent pump controller
Hide thumbs Also See for iQpump1000:
Table of Contents

Advertisement

B.3 b: Application
No.
(Addr.
Name
Hex)
b1-16
Run Command
(01C5)
Selection 2
<1>
Run Source 2
b1-17
Run Command at Power
(01C6)
Up
<1> Available in drive software versions PRG: 8551 and later.
<2> Available in drive software versions PRG: 8552 and later. Not available in drive models 4A0930 and 4A1200.
u
b2: DC Injection Braking and Short Circuit Braking
No.
(Addr.
Name
Hex)
b2-01
DC Injection Braking
(0189)
Start Frequency
b2-02
DC Injection Braking
(018A)
Current
b2-03
DC Injection Braking
(018B)
Time at Start
b2-04
DC Injection Braking
(018C)
Time at Stop
b2-08
Magnetic Flux
(0190)
Compensation Value
u
b3: Speed Search
No.
(Addr
Name
Hex.)
b3-01
Speed Search Selection
(0191)
at Start
b3-02
Speed Search
(0192)
Deactivation Current
b3-03
Speed Search
(0193)
Deceleration Time
b3-04
V/f Gain during Speed
(0194)
Search
b3-05
Speed Search Delay
(0195)
Time
354
LCD DIsplay
Enabled when a multi-function digital input set for "External
Run Source 2
Reference" (H1-oo = 2) closes.
0: Operator
0: Operator
1: Digital Inputs
1: Digital Inputs
2: Communication
2: Communication
3: Option PCB
3: Option PCB
6: AUTOKey + Term
6: AUTOKey + Term
7: AUTOKey + Serial
7: AUTOKey + Serial
8: AUTOKey + Option
8: AUTOKey + Option
0: Disregarded. A new Run command must be issued after
Run Cmd @ Pwr On
power up.
0: Cycle Ext Run
1: Allowed. Motor will start immediately after power up if a
1: Accept Ext Run
Run command is already enabled.
LCD Display
Sets the frequency at which DC Injection Braking starts when
DCInj Start Freq
"Ramp to stop" (b1-03 = 0) is selected.
Sets the DC Injection Braking current as a percentage of the
DCInj Current
drive rated current.
Sets DC Injection Braking time at start. Disabled when set to
DCInj Time@Start
0.00 seconds.
Sets DC Injection Braking time at stop.
DCInj Time@Stop
OLV
OLV
OLV
OLV
Field Comp
Sets the magnetic flux compensation as a percentage of the no-
load current value (E2-03).
LCD Display
SpdSrch at Start
0: Disabled
0: Disabled
1: Enabled
1: Enabled
Sets the current level at which the speed is assumed to be
detected and Speed Search is ended. Set as a percentage of the
SpdSrch DeactCur
drive rated current.
Sets output frequency reduction time during Speed Search.
SpdSrch Dec Time
Determines how much to lower the V/f ratio during Speed
Search.
SpdSrch V/f
Output voltage during Speed Search equals the V/f setting
multiplied by b3-04.
When using an external contactor on the output side, b3-05
Search Delay
delays executing Speed Search after a momentary power loss to
allow time for the contactor to close.
Description
<2>
<2>
<2>
Description
Description
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual
Values
Page
Default: 0
Range: 0 to 3; 6
to 8
Default: 1
Range: 0, 1
Values
Page
Default: 0.5 Hz
Min.: 0.0
Max.: 10.0
Default: 50%
Min.: 0
Max.: 100
Default: 0.00 s
Min.: 0.00
Max.: 10.00
Default: 0.50 s
Min.: 0.00
Max.: 10.00
Default: 0%
Min.: 0
Max.: 1000
Values
Page
Default: 0
220
Range: 0, 1
Default: 120%
(V/f)
100% (OLV)
Min.: 0
Max.: 200
Default: 2.0 s
Min.: 0.1
Max.: 10.0
<1>
Default:
Min.: 10%
Max.: 100%
Default: 0.2 s
Min.: 0.0
Max.: 100.0