YASKAWA iQpump1000 User Manual page 447

Ac drive intelligent pump controller
Hide thumbs Also See for iQpump1000:
Table of Contents

Advertisement

u
U6: Operation Status Monitors
No.
(Addr.
Name
Hex)
U6-01
Motor Secondary
(0051)
Current (Iq)
U6-02
Motor Excitation
(0052)
Current (Id)
U6-05
Output Voltage
(0059)
Reference (Vq)
U6-06
Output Voltage
(005A)
Reference (Vd)
U6-07
q-Axis ACR Output
(005F)
U6-08
d-Axis ACR Output
(0060)
<1> Values shown are specific to 200 V class drives. Double the values for 400 V class drives. Multiply the values by 2.875 for 600 V class drives.
Note:
Fault histories are not kept when CPF00, CPF01, CPF06, CPF24, oFA00, oFb00, oFC00, Uv1, Uv2, or Uv3 occur.
u
U7: CASE Monitors
No.
(Addr.
Name
Hex)
U7-01
CASE Software
(0051)
Number
u
U9: Operation Status Monitors
No.
(Addr.
Name
Hex)
U9-01
Network PI Feedback
(1901)
U9-02
(1902)
Network Activity
<2>
U9-03
(1903)
Time to Alternate
<2>
U9-04
Running Queue
(1904)
Number
<1> Unit changes based on network status.
<->: Drive cannot communicate to other drives
<+>: Drive is a node on a network
<M>: Drive is the master on an iQpump network.
<2> Monitor is available through the Quick Monitor screen.
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual
LCD Display
Displays the value of the motor secondary current (Iq). Motor
Mot SEC Current
rated secondary current is 100%.
OLV
OLV
OLV
OLV
Mot EXC Current
Displays the value calculated for the motor excitation current
(Id). Motor rated secondary current is 100%.
OLV
OLV
OLV
OLV
Voltage Ref (Vq)
Output voltage reference (Vq) for the q-Axis.
OLV
OLV
OLV
OLV
Voltage Ref (Vd)
Output voltage reference (Vd) for the d-Axis.
OLV
OLV
OLV
OLV
ACR(q) Output
Displays the output value for current control relative to motor
secondary current (q-Axis).
OLV
OLV
OLV
OLV
ACR(d) Output
Displays the output value for current control relative to motor
secondary current (d-Axis).
LCD Display
Displays the CASE software version number.
CASE Software #
LCD Display
Displays the network PI feedback recognized by the iQpump
Net PI Feedback
MEMOBUS network.
Displays network traffic. A fluctuating number from 0 to 10000
denotes activity, while a relatively constant 0 denotes no
iQ Net Activity
activity.
Displays the time remaining before a drive requests the
alternation mode set in P9-04.
Time to Alternate
Displays the position in the iQPump MEMOBUS Multiplex
Running Queue No
running queue.
Description
Description
Description
B.16 U: Monitors
Analog
Unit
Output Level
10 V: Motor
secondary rated
0.1%
current
10 V: Motor
secondary rated
0.1%
current
10 V: 200 Vrms
0.1 Vac
<1>
10 V: 200 Vrms
0.1 Vac
<1>
10 V: 200 Vrms
0.1%
<1>
110 V: 200
0.1%
<1>
Vrms
Analog
Unit
Output Level
No signal output
available
Analog
Unit
Output Level
No signal output
Dep. on
available
P1-02
No signal output
<1>
available
No signal output
min
available
No signal output
available
B
447

Hide quick links:

Advertisement

Table of Contents
loading