• Only the Lead drive can request staging and de-staging.
• Staging will start a new Lead drive and make the old Lead drive into a Lag drive.
• De-staging will stop the current Lead drive and restore the previous drive as the Lead drive.
n
Multiplexing Messages
During multiplexing, the drive will display a message when it will be staged in or de-staged out. The message will indicate if
it is being staged in or out and display a countdown timer of how long until the change takes place.
One of the following conditions must be met for de-staging to occur:
• High Feedback Quick De-stage
• Low Feedback Quick De-stage
• Normal De-stage
• Low Water Level De-stage
• Suction Pressure De-stage
n
Drive Run Order
U9-04, Running Queue No:
• Shows the position in the iQpump MEMOBUS running queue.
• U9-04 = 0 for pumps that are not running.
• U9-04 = 1 on the first pump that came on and is still running.
• U9-04 = 2 on the second pump that came on and is still running.
• U9-04 = the number of pumps running for the current Lead drive.
n
Multiplex Status Display
Network State
Drive is not able to accept commands from
the iQpump MEMOBUS network because
the drive is not in AUTO Mode run.
Drive is in AUTO Mode and waiting for a run
command from the iQpump MEMOBUS
network.
Drive is in AUTO Mode, Lead operation and
is currently regulating the system using PI
control.
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual
Table 4.9 Multiplex Status Display
- MODE -
Pump Off Network
U5-99= 100.0
U1-02=
U1-91=
Home
- MODE -
Wait for Net Cmd
U5-99= 100.0
U1-02=
U1-91=
Home
- MODE -
Lead: Setpoint
U5-99= 100.0
U1-02=
U1-91=
Home
4.6 iQpump Presets and Functions
Display
DRV RDY
PSI
0.00Hz
62.8PSI
DRV RDY
PSI
0.00Hz
62.8PSI
DRV RDY
PSI
52.38Hz
62.8PSI
4
181