YASKAWA iQpump1000 User Manual page 387

Ac drive intelligent pump controller
Hide thumbs Also See for iQpump1000:
Table of Contents

Advertisement

No.
(Addr.
Name
Hex)
H5-12
Run Command Method
(043D)
Selection
H5-13
(043E)
Power-up CALL Alarm
<3>
H5-14
(0FB4)
Communication Error
(CE) Go-To- Frequency
<3>
H5-15
(0FB5)
Communication Error
(CE) Go-To-Timeout
<3>
H5-16
Communication Error
(0FB6)
Fault Restart Selection
<3>
<1> If this parameter is set to 0, the drive will be unable to respond to MEMOBUS/Modbus commands.
<2> When P1-01, Pump Mode, is set to 3 (MEMOBUS network), the range is dependent on P9-25, Highest Node Address.
<3> Available in drive software versions PRG: 8552 and later. Not available in drive models 4A0930 and 4A1200.
u
H6: Pulse Train Input
No.
(Addr.
Name
Hex)
Pulse Train Input
H6-01
Terminal RP Function
(042C)
Selection
H6-02
(042D) Pulse Train Input
Scaling
H6-03
(042E)
Pulse Train Input Gain Terminal RP Gain
H6-04
(042F)
Pulse Train Input Bias
H6-05
Pulse Train Input Filter
(0430)
Time
H6-08
Pulse Train Input
(043F)
Minimum Frequency
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual
LCD Display
Run CommandSel
0: FWD/Stop, REV/Stop
0: FWD Run &REV
1: Run/Stop, FWD/REV
Run
1: Run & FWD/REV
Determines whether a CALL alarm is triggered at power-up
Powr-up CALL Alm
when communication with the external controller has not been
0: Disabled
established.
1: Enabled
0: Disabled
1: Enabled
Sets the speed at which the drive will run when H5-04 is set to
CE Go-To-Freq
4 (Run at H5-14) and a CE error is present.
Sets the amount of time that the drive will run at the speed set
in H5-14 before triggering a CE fault when H5-04 is set to 4
CE Go-To-Timeout
(Run at H5-14) and a CE error is present.
Setting this parameter to 0 will disable the time-out.
CE Fault Restart
Determines whether the CE fault can be restarted (L5-01).
0: No Retry
0: No Retry
1: Retry
1: Retry
LCD Display
0: Frequency reference
Term RP Func Sel
1: PID feedback value
0: Frequency Ref
2: PID setpoint value
1: PID Feedback
5: Flow meter
2: PID Set Point
Note:
5: Flow Meter
Sets the terminal RP input signal frequency that is equal to 100%
of the value selected in H6-01.
Term RP Scaling
Sets the level of the value selected in H6-01 when a frequency
with the value set in H6-02 is input.
Sets the level of the value selected in H6-01 when 0 Hz is input. Default: 0.0%
Terminal RP Bias
Sets the pulse train input filter time constant.
Term RP Flt Time
Sets the minimum frequency for the pulse train input to be
RP Lower Limit
detected. Enabled when H6-01 = 0, 1, or 2.
B.8 H Parameters: Multi-Function Terminals
Description
Description
When this parameter is set to 5, parameters H6-02
to H6-04 and H6-08 are ignored.
Values
Page
Default: 0
457
Range: 0, 1
Default: 0
Range: 0, 1
Default: 0.0 Hz
Min.: 0.0
457
Max.: 400.0
Default: 0 s
Min.: 0
457
Max.: 6000
Default: 0
457
Range: 0, 1
Values
Page
Default: 0
Range: 0 to 2; 5
Default: 1440 Hz
Min.: 100
Max.: 32000
Default: 100.0%
Min.: 0.0
Max.: 1000.0
Min.: -100.0
Max.: 100.0
Default: 0.50 s
Min.: 0.00
Max.: 2.00
Default: 0.5 Hz
Min.: 0.1
Max.: 1000.0
B
387