YASKAWA iQpump1000 User Manual page 502

Ac drive intelligent pump controller
Hide thumbs Also See for iQpump1000:
Table of Contents

Advertisement

D.2 UL and CSA Standards
<5> Class L fuse is also approved for this rating.
Wiring Fuses for Models 4A0930 and 4A1200
NOTICE: If a fuse is blown or an Ground Fault Circuit Interrupter (GFCI) is tripped, check the wiring and the selection of peripheral devices
to identify the cause. Contact Yaskawa before restarting the drive or the peripheral devices if the cause cannot be identified.
Install a fuse on the input side to protect drive wiring and prevent other secondary damage. Wire the fuse so that leakage
current in the upper controller power supply will trigger the fuse and shut off the power supply.
Select the appropriate fuse from
Voltage
Model
Class
Input Voltage
Three-
4A0930
480 V
Phase
400 V
Class
4A1200
480 V
n
Low Voltage Wiring for Control Circuit Terminals
Wire low voltage wires with NEC Class 1 circuit conductors. Refer to national state or local codes for wiring. The external
power supply shall be a UL listed Class 2 power supply source or equivalent only.
Input / Output
Digital inputs
Analog inputs / outputs
n
Drive Short Circuit Rating
The drive is suitable for use on a circuit capable of delivering not more than 100,000 RMS symmetrical Amperes, 240 Vac
maximum (200 V Class), 480 Vac maximum (400 V Class), and 600 Vac maximum (600 V Class) when protected by Bussmann
Type FWH or FWP fuses as specified in
502
Table
3.2.
Table D.6 Input Fuses for Models 4A0930 and 4A1200
Selection
Pre-arc
Current
2
I
t (A
140000 to
1500 A
3100000
320000 to
1500 A
3100000
Table D.7 Control Circuit Terminal Power Supply
Terminal Signal
S1 to S8, SC
+V, A1, A2, A3, AC, AM, FM
Factory Recommended Branch Circuit Protection
Model
Manufacturer
2
s)
CS5F-1200
Fuji Electric
FWH-1200A
Bussman
CS5F-1500
Fuji Electric
FWH-1600A
Bussman
Use the internal LVLC power supply of the drive. Use class
2 for external power supply.
Use the internal LVLC power supply of the drive. Use class
2 for external power supply.
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual
Input Fuse (Example)
Rating
AC500 V, 1200 A
AC500 V, 1200 A
AC500 V, 1500 A
AC500 V, 1600 A
Power Supply Specifications
on page 488.
Pre-arc
2
2
I
t (A
s)
276000
351000

Hide quick links:

Advertisement

Table of Contents
loading