B.9 L: Protection Function
No.
(Addr.
Name
Hex)
L2-10
KEB Detection Time
(048E)
(Minimum KEB Time)
L2-11
DC Bus Voltage
(0461)
Setpoint during KEB
L2-29
KEB Method Selection
(0475)
<1> Default setting is dependent on parameter o2-04, Drive Model Selection.
<2> Default setting is dependent on parameter E1-01, Input voltage Setting.
<3> Values shown are specific to 200 V class drives. Double the value for 400 V class drives. Multiply the value by 2.875 for 600 V class drives.
<4> Setting range value is dependent on parameter C1-10, Accel/Decel Time Setting Units. When C1-10 = 0 (units of 0.01 seconds), the setting range
becomes 0.00 to 600.00 seconds.
<5> Values shown are specific to 200 V class drives. Double the value for 400 V class drives. Multiply the value by 2.875 for 600 V class drives, but
set the value below 1040 Vdc (overvoltage protection level).
u
L3: Stall Prevention
No.
(Addr.
Name
Hex)
Stall Prevention
L3-01
Selection during
(048F)
Acceleration
L3-02
Stall Prevention Level
(0490)
during Acceleration
L3-03
Stall Prevention Limit
(0491)
during Acceleration
Stall Prevention
L3-04
Selection during
(0492)
Deceleration
L3-05
Stall Prevention
(0493)
Selection during Run
L3-06
Stall Prevention Level
(0494)
during Run
390
LCD Display
Sets the time to perform KEB Ride-Thru.
KEB Detect Time
Sets the desired value of the DC bus voltage during KEB Ride-
Thru.
KEB DC Bus Level
KEB Mode Sel
0: Single Drive KEB Ride-Thru 1
0: Single Mode KEB1
1: Single Drive KEB Ride-Thru 2
1: Single Mode KEB2
2: System KEB Ride-Thru 1
2: System Mode
3: System KEB Ride-Thru 2
KEB1
3: System Mode
KEB2
LCD Display
0: Disabled.
StallP Accel Sel
1: General purpose. Acceleration is paused as long as the current
0: Disabled
is above the L3-02 setting.
1: General Purpose
2: Intelligent. Accelerate in the shortest possible time without
2: Intelligent
exceeding the L3-02 level.
Used when L3-01 = 1 or 2. 100% is equal to the drive rated
current.
StallP Accel Lvl
Sets Stall Prevention lower limit during acceleration when
StallPAcc LowLim
operating in the constant power range. Set as a percentage of
drive rated current.
0: Disabled. Deceleration at the active deceleration rate. An ov
fault may occur.
1: General purpose. Deceleration is paused when the DC bus
voltage exceeds the Stall Prevention level.
StallP Decel Sel
2: Intelligent. Decelerate as fast as possible while avoiding ov
0: Disabled
faults.
1: General Purpose
3: Stall Prevention with braking resistor. Stall Prevention during
2: Intelligent
deceleration is enabled in coordination with dynamic braking.
3: StallP +Resistor
4: Overexcitation Deceleration. Decelerates while increasing
4: High Flux Brake
the motor flux.
5: High Flux Brake2
5: Overexcitation Deceleration 2. Adjust the deceleration rate
according to the DC bus voltage.
Note:
0: Disabled. Drive runs at a set frequency. A heavy load may
StallP Run Sel
cause speed loss.
0: Disabled
1: Decel time 1. Uses the deceleration time set to C1-02 while
1: Decel Time
Stall Prevention is performed.
2: Decel Time 2
2: Decel time 2. Uses the deceleration time set to C1-04 while
Stall Prevention is performed.
V/f
V/f
StallP Run Level
Enabled when L3-05 is set to 1 or 2. 100% is equal to the drive
rated current.
Description
Description
Setting 3 is not available in models 4A0930 and
4A1200.
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual
Values
Page
Default: 50 ms
Min.: 0
Max.: 2000
<2>
Default:
[E1-01] × 1.22
Min.: 150 Vdc
Max.: 400 Vdc
<5>
Default: 0
Range: 0 to 3
Values
Page
Default: 1
Range: 0 to 2
<1>
Default:
Min.: 0%
<1>
Max.: 150%
Default: 50%
Min.: 0
Max.: 100
Default: 0
Range: 0 to 5
Default: 0
Range: 0 to 2
<1>
Default:
Min.: 30%
<1>
Max.: 150%