YASKAWA iQpump1000 User Manual page 147

Ac drive intelligent pump controller
Hide thumbs Also See for iQpump1000:
Table of Contents

Advertisement

A1-03 = 6013
(A1-06 = 13)
Advanced Pressure Control
Parameter
Value
A1-02
0
<1> Default is 100.0 PSI in drive software versions PRG: 8553 and earlier.
<2> Available in drive software versions PRG: 8554 and later.
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual
A1-03 = 6014
(A1-06 = 14)
Pivot Panel Submersible
Parameter
Value
A1-02
0
b1-02
1
b1-03
0
b5-03
5.0 s
C1-01
20.0 s
C1-02
20.0 s
E1-04
65.0 Hz
L2-01
0
L5-01
0
L5-04
300.0 s
<1>
P1-03
200.0 PSI
<2>
210.0 PSI
P1-11
P1-40
60.0 Hz
P2-03
15 s
P2-23
0.00%
P5-01
0
P5-02
6.0 Hz
4.5 Pump Application Presets
A1-03 = 7770
(A1-06 = 1)
General Purpose
Parameter
Value
b1-01
1
b1-02
1
b5-01
0
C1-01
25.0 s
C1-02
25.0 s
H1-06
4
H1-07
F
H2-01
0
H2-02
A
H3-10
2
L5-01
0
L5-04
180.0 s
o1-06
0
P1-05
0 sec
P1-06
0.0 Hz
P4-12
0.0 Hz
P4-17
0.0 min
P5-02
0.0 Hz
A1-03 = 7771
(A1-06 = 2)
Sub Mtr GP Oper
Parameter
Value
A1-02
0
b5-01
0
H1-06
4
H2-01
0
H2-02
A
o1-06
0
P1-05
0 s
d1-01
40.00 Hz
147