B.9 L: Protection Function
B.9 L: Protection Function
L parameters provide protection to the drive and motor, including control during momentary power loss, Stall Prevention,
frequency detection, fault restarts, overtorque detection, and other types of hardware protection.
u
L1: Motor Protection
No.
(Addr.
Name
Hex)
L1-01
Motor Overload
(0480)
Protection Selection
L1-02
Motor Overload
(0481)
Protection Time
Motor Overheat Alarm
L1-03
Operation Selection
(0482)
(PTC input)
Motor Overheat Fault
L1-04
Operation Selection
(0483)
(PTC input)
Motor Temperature
L1-05
Input Filter Time (PTC
(0484)
input)
Continuous
L1-13
Electrothermal
(046D)
Operation Selection
L1-15
Motor 1 Thermistor
(0440)
Selection (NTC)
L1-16
Motor 1 Overheat
(0441)
Temperature
L1-17
Motor 2 Thermistor
(0442)
Selection (NTC)
L1-18
Motor 2 Overheat
(0443)
Temperature
388
LCD Display
0: Disabled
Mtr OL Charact
1: General purpose motor (standard fan cooled)
0: OL1 Disabled
2: Drive dedicated motor with a speed range of 1:10
1: VT Motor
3: Vector motor with a speed range of 1:100
2: CT Motor
6: General purpose motor (50 Hz)
3: Vector Motor
The drive may not be able to provide protection when using
6: 50Hz VT Motor
multiple motors, even if overload is enabled in L1-01. Set L1-01
to 0 and install separate thermal relays to each motor.
Sets the motor thermal overload protection (oL1) time.
MOL Time Const
Sets operation when the motor temperature analog input (H3-02,
Mtr OH Alarm Sel
H3-10, or H3-06 = E) exceeds the oH3 alarm level.
0 : Ramp to Stop
0: Ramp to stop
1: Coast to Stop
1: Coast to stop
2: Fast-Stop
2: Fast Stop (decelerate to stop using the deceleration time in
3: Alarm only
C1-09)
3: Alarm only ("oH3" will flash)
Sets stopping method when the motor temperature analog input
Mtr OH Fault Sel
(H3-02, H3-10, or H3-06 = E) exceeds the oH4 fault level.
0 : Ramp to Stop
0: Ramp to stop
1: Coast to Stop
1: Coast to stop
2: Fast-Stop
2: Fast Stop (decelerate to stop using the deceleration time in
C1-09)
Adjusts the filter for the motor temperature analog input (H3-02,
Mtr Temp Filter
H3-10, or H3-06 = E).
Mtr OL Mem Sel
0: Disabled
0: Disabled
1: Enabled
1: Enabled
2: Enabled (RTC)
2: Enabled(RTC)
0: Disabled
1: Enabled
M1 OH5 Fault Sel
Note:
Sets the temperature for motor 1 that triggers an overheat fault
(oH5).
M1 OH5 level
Note:
0: Disabled
1: Enabled
M2 OH5 Fault Sel
Note:
Sets the temperature for motor 1 that triggers an overheat fault
(oH5).
M2 OH5 level
Note:
Description
This parameter is only available in models
4A0930 and 4A1200.
This parameter is only available in models
4A0930 and 4A1200.
This parameter is only available in models
4A0930 and 4A1200.
This parameter is only available in models
4A0930 and 4A1200.
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual
Values
Page
Default: 1
Range: 0 to 3; 6
Default: 1.0 min
Min.: 0.1
Max.: 5.0
Default: 3
Range: 0 to 3
Default: 1
Range: 0 to 2
Default: 0.20 s
Min.: 0.00
Max.: 10.00
<1>
Default: 2
Range: 0 to 2
Default: 0
Range: 0, 1
Default: 120 °C
Min.: 50
Max.: 200
Default: 0
Range: 0, 1
Default: 120 °C
Min.: 50
Max.: 200